IM 77J04R31-01E 2nd Edition  Oct. 15, 2019-00

7

13.  MONITOR OUTPUT 

13.1 Monitor Output (Analog) 

Monitor output (analog) is added only when monitor output code “6” or “A” is specified at the time of 

order. 

13.1.1  Setting Monitor Output 

In setting monitor output, the maximum monitor output value (RTH) and minimum monitor output 

value (RTL) can be freely set within the instrument input range of the set range code No. (IN) that 

have been set for the MVRK. 

For example, to set the monitor output corresponding to the measured input range “-50.0 to 150.0°C” 

to “1 to 5 V DC” when the MVRK range code No. (IN) is “62” (instrument input range: -199.9 to 

200.0°C), set the maximum monitor output value (RTH) to “150.0” and the minimum monitor output 

value (RTL) to “-50.0.” This causes monitor output to be “1 V” when input to the MVRK is 50.0°C as 

shown below. 

 

-199.9°C

1V

200.0°C

5V

-50.0

(RTL)

150.0

(RTH)

Range code No. 62

Monitor output setting

Maximum monitor output value: 150.0°

C

 

Minimum monitor output value:  -50.0°

C

 

Input range available for the range 

code No. 62 of the MVRK

Monitor output range

Fixed to 4 to 20 mA or 1 to 5 V DC

(5 V is output when the measured value is150.0°

C

,

while 1 V is output when it is -50.0°

C

.) 

13.1.2   Setting Ranges and Factory-Set Values of Monitor Output (Analog)-Related 

Parameters 

Setup Parameter Screen 2

Parameter 

Symbol

Parameter Name

Setting Range

Factory-Set 

Value

Maximum monitor output 

value (RTH)

RTL + 1 digit to 9999

Within the instrument input range

Maximum value 

of the instrument 

input range

Minimum monitor output 

value (RTL)

-1999 to RTH - 1 digit

Within the instrument input range

Minimum value 

of the instrument 

input range

Visibility of monitor output 

adjustment screen (MON)

OFF (invisible) or ON (visible)

Set this parameter to “ON” for adjustments of monitor 

output.

OFF

(invisible)

Forced output of a monitor 

output value (MAN)

-25.0 to +125.0 (%)

Note that the assured range is -6.0 to +106 (%).

0.0

Monitor output zero 

adjustment (ZER)

-19.99 to 20.00 (%)

0.00

Monitor output span 

adjustment (SPN)

-19.99 to 20.00 (%)

0.00

13.1.3  Setting Monitor Output 

 CAUTION

Accuracy (±0.1% of output span) is limited depending on the settings for maximum and 

minimum monitor output values. For more information on accuracy limitations, refer to 

the general specifications (GS 77J04R31-01E). 

This subsection describes an example of setting the maximum monitor output value (RTH) to “150.0” 

and minimum monitor output value (RTL) to “-50.0” when the MVRK range code No. is set to “62.”

When you press the SET/ENT key for more than 3 sec. 

with the Operation Parameter Screen displayed, the Setup 

Parameter Screen 1 appears. 

When the power is turned on, the PV screen of the 

Operation Parameter Screen appears. 

Press the SET/ENT key to display parameter "RTH."

In this case, the DATA display shows "200.0," the 

maximum value of instrument input range of the range 

code No.  "62." 
 

Press the DOWN key to display "150.0" on the DATA 

display. 

Press the SET/ENT key to accept this data. 

This completes the procedure for setting the maximum 

monitor output value.
Press the SET/ENT key to display the next parameter. 

Press this key for 

more than 3 sec. 

The decimal point blinks during 

data change.

The decimal point blinks during 

data change.

Press the SET/ENT key to display parameter "LOC." 

Press the DOWN key to display "-1" on the DATA display. 

Press the SET/ENT key to display the Setup Parameter 

Screen 2.

Press the SET/ENT key to display parameter "RTL."

In this case, the DATA display shows "-199.9," the 

minimum value of instrument input range of the range code 

No. "62."  
 

Press the UP key to display "-50.0" on the DATA display. 

Press the SET/ENT key to accept this data. 

This completes the procedure for setting the minimum 

monitor output value.

The decimal point blinks during 

data change.

Setup Parameter Screen 1 

Setup Parameter Screen 2

Operation Parameter Screen

Power ON 

This completes the procedure 

for setting the maximum 

monitor output value. 

This completes the procedure 

for setting the minimum monitor 

output value. 

Press               to display 

 "LOC." 

Press              to display 

 "-1." 
 

Press              .

Press              to display 

 "RTL." 

 

Press             to display 

 "-50.0."
 

Press             . 

Press              to display 

 "RTH." 

 

Press             to display 

 "150.0."

 
 

Press             . 

 
Press             . 

13.1.4  Adjusting Monitor Output 

(1) Instruments for adjustment 

 •

Digital multimeter (DMM) (YOKOGAWA DM7560 or the equivalent): 1

 •

Precision resistor of 250 Ω ± 0.01%, 0.25 W or more: 1

(2) Output adjustments 

Connect each instrument as shown below. 

 

10 11

1 2

3

9

8 7

6 5

4

7
8

N–

L+

(SUPPLY)

Power supply

R: 250 

 precision resistor for current 

output

R

DMM

Main unit

Socket

+

1

1
3

3

Monitor output 

(3) Adjusting monitor output 

  The following describes an example of adjusting an error when the minimum monitor output value 

(measured value) is 1.008 V (an error of 0.008 V) with the MVRK monitor output set to “1 to 5 V 

DC.” The basic adjusting procedure for the maximum monitor output value is the same as that of 

the minimum monitor output value; perform it by referring to the procedure below. 

  The procedure below begins with the condition in which the Setup Parameter Screen 2 is 

displayed.

Press the SET/ENT key to display parameter "MON." 
 

Press the UP key to display "ON" on the DATA display. 

Press the SET/ENT key to accept the data. 

Press the SET/ENT key twice to display parameter "ZER."

Display parameter "MON" and press the DOWN key to 

display "OFF" on the DATA display. 

 

Press the SET/ENT key to accept the data. 

Press the UP key to display "-0.20" on the DATA display. 

Then press the UP or DOWN key to make fine 

adjustments. 

Make adjustments to the maximum monitor output value 

by displaying parameter "SPN." 

The minimum output value

 (1 V) is output forcibly. 

The maximum output 

value (5 V) is output 

forcibly.  

(Displays a correction value 

corresponding to the error.) 

Press             to display 

 "-0.20." 
Press             or 
to make fine adjustments. 

Setup Parameter Screen 2

This establishes the setting in which 

the monitor output adjustment 

screen becomes visible. 

This establishes the setting in which 

the monitor output adjustment 

screen becomes invisible. 

This completes the process for 

adjusting the minimum monitor 

output value. 

The MVRK enters the operable status as soon as the power is turned on, but requires 10 to 15 minutes 

of warm-up to meet the performance requirements. 

(Measured value [1.008 V]) - (Reference value [1 V])

Output span [4 V]

×

 100 (%)

Error =

Follow the same procedure as above to adjust the maximum monitor 

output value. 

After adjusting the monitor output, set the MON parameter to "OFF" (making the adjustment 

screen invisible). 

When this parameter (ZER) is displayed, the MVRK forcibly outputs 
the minimum monitor output value (0%), regardless of input.

The monitor output is corrected by -0.2% because the error is 

+0.008 V (+0.2%). 

Press               to display 

 "MON." 

 

Press             to display 

 "ON."

Press             . 

 

Press              to display 

 "ZER." 

Press             to display 

 "OFF." 

 

Press             . 

13.1.5  Using the Forced Output Function 

The use of the forced output function allows you to conduct operation tests for a device 

connected to the monitor output terminals of the MVRK. 

This subsection describes an example of forcing a value equivalent to 50% of the output 

range (3 V) to output when the monitor output of the MVRK is “1 to 5 V DC.” 

The procedure below begins with the condition in which parameter “MAN” is displayed 

with the MON parameter set to “ON” in the Setup Parameter Screen 2. 

Press the UP key to display "50.0" on the DATA display. 

The minimum output value

 (1 V) is output forcibly. 

The value equivalent to 

50% of the output range 

(3 V) is output forcibly.  

Setup Parameter Screen 2

When this parameter (MAN) is displayed, the MVRK forces 

the monitor output value to be output, regardless of input.

3 V is output forcibly.  The MVRK continues to output 

while this parameter is displayed on the screen.

After completion of the forced output, return the MON parameter setting to "OFF" (making the 

adjustment screen invisible). 

Pressing              causes 
the output value to increase.

 CAUTION

After performing monitor output adjustments or forced output, always set the MON 

parameter to “OFF” (making the adjustment screen invisible). If the Setup Parameter 

Screen 2 is switched while the MON parameter is set to “ON,” displaying parameter 

“MAN,” “ZER” or “SPN” causes a value corresponding to the set value to be output 

forcibly. Furthermore, if the power is turned off while parameter “MAN” is displayed, the 

set values will be initialized. 

Содержание JUXTA MVRK

Страница 1: ...lly to the socket face Otherwise the terminals may bend and it may cause bad contact The converter shall not tilt 5 degrees or more in either direction when installed When the converter is not connect...

Страница 2: ...5 PART NAMES OF FRONT PANEL AND THEIR FUNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage 1 PV measured value display Place for a...

Страница 3: ...rm 3 hysteresis HY3 Displayed only for 4 points of alarms Sets the hysteresis of alarm 3 Alarm 4 hysteresis HY4 Displayed only for 4 points of alarms Sets the hysteresis of alarm 4 Alarm ON delay OND...

Страница 4: ...ion describes how to correct wiring resistance when an error occurs due to the influence of the input wiring resistance Correct wiring resistance after completing the wiring 5 4 6 A B B Short circuit...

Страница 5: ...f Adjustment Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Input adjustment reset RST OFF 0 or ON 1 This parameter is used set to ON to re...

Страница 6: ...ay color mode 6 Press the SET ENT key for more than 3 sec This causes the Operation Parameter Screen to appear Setting the PV display color mode Setup Parameter Screen 2 Continue to the upper right Pr...

Страница 7: ...Press to display RTL Press to display 50 0 Press Press to display RTH Press to display 150 0 Press Press 13 1 4 Adjusting Monitor Output 1 Instruments for adjustment Digital multimeter DMM YOKOGAWA DM...

Страница 8: ...lay 1 Press Press to display PSL Press or to display the communication protocol number to use Press Press Press the DOWN key to display 1 on the DATA display Press the SET ENT key to display the Setup...

Отзывы: