7.  SWITCHING PARAMETERS

 CAUTION

 

If the alarm action (AL1 to AL4) is set to "OFF," the relevant alarm setpoint (A1 to A4) 

is not displayed.

 

If no keystroke is made for more than 2 minutes, the PV screen automatically 

appears, regardless of the parameter displayed. In this case, if a data change is in 

progress (the decimal point is blinking), the data being changed becomes invalid and 

the PV screen appears with the previous data displayed as is. However, this action 

does not take place if the parameter "MAN", "ZER" or "SPN" is being displayed.

Operation Parameter Screen

Setup Parameter Screen 1

Setup Parameter Screen 2

To the Operation Parameter Screen

A

A

A

Press this key for more than 3 sec.

Press this key

for more than 3 sec.

Press this key 

for more than 3 sec.

is displayed when the PV display color mode (PCM) has 

been set to 6, 7, 8 or 9. 

A

D

C

B

B

C

D

D

C

or

Press the DOWN key to display "-1" 

on the DATA display and then press 

the SET/ENT key.

Power 

ON

Displays a measured value.

 

In this manual, this screen is called the "PV 

(measured value) screen." 

Alarm-1 setpoint (A1)

Sets the alarm-1 setpoint.

Alarm-2 setpoint (A2)

Sets the alarm-2 setpoint.

Alarm-3 setpoint (A3)

(Displayed only for 4 points of alarms) 

Sets the alarm-3 setpoint.

Alarm-4 setpoint (A4)

(Displayed only for 4 points of alarms) 

Sets the alarm-4 setpoint.

Alarm-1 action (AL1)

Sets the direction of alarm-1 action. 

(See the Alarm Action Type Codes table in Section 9.1.)

Range code No. (IN)

Sets the range code number (input type). 

Measured input bias (BS)

This parameter is set to correct a measured 

input value.

PV display color mode (PCM)

Sets the Active color PV display.

Economical mode time (ECO)

This parameter is set to extinguish the display 

(not including the READY and alarm lamps) if no 

keystroke is made for a specified time. 

Input adjustment reset (RST)

Used to reset an input adjustment value. 

Input adjustment point LOW (BL)

Sets the reference value corresponding to 

0% of the input when an input adjustment is 

made.

Input adjustment LOW (AL)

Adjusts the 0% value of an input.

Input adjustment point HIGH (BH)

Sets the reference value corresponding to 

100% of the input when an input adjustment 

is made.

Input adjustment HIGH (AH)

Adjusts the 100% value of an input.

Alarm-2 action (AL2)

Sets the direction of alarm-2 action.

(See the Alarm Action Type Codes table in Section 9.1.)

Alarm-3 action (AL3)

(Displayed only for 4 points of alarms) 

Sets the direction of alarm-3 action.

(See the Alarm Action Type Codes table in Section 9.1.)

Alarm-4 action (AL4)

(Displayed only for 4 points of alarms) 

Sets the direction of alarm-4 action.

(See the Alarm Action Type Codes table in Section 9.1.)

Alarm-1 hysteresis (HY1)

Sets the hysteresis of alarm 1.

Alarm-2 hysteresis (HY2)

Sets the hysteresis of alarm 2. 

Alarm-3 hysteresis (HY3)

(Displayed only for 4 points of alarms) 

Sets the hysteresis of alarm 3.

Alarm-4 hysteresis (HY4)

(Displayed only for 4 points of alarms) 

Sets the hysteresis of alarm 4. 

Alarm ON delay (OND)

Sets the condition monitoring time from the 

establishment of alarm conditions to its

output.

Alarm OFF delay (OFD)

Sets the condition monitoring time from the 

establishment of return-to normal conditions 

to its output. 

Setpoint (SP)

When using a deviation alarm, this 

parameter is set to the value treated as the 

reference for deviations. 

Key lock (LOC)

This parameter is set when change of parameter 

settings (all parameters or parameters other than the 

operation parameters) is locked to prevent wrong 

operations.

Visibility of monitor output adjustment screen (MON)

Sets the visibility of the screen for adjusting monitor 

output.  Pressing the SET/ENT key with "ON" 

displayed on the DATA display causes the 

adjustment screen to appear.

Forced output of a monitor output value (MAN)

Used to force a value equivalent to -25% to +125% 

of an analog output value to output, regardless of 

input.

Monitor output zero adjustment (ZER

)

Adjusts the zero point of the monitor output. 

Monitor output span adjustment (SPN

)

Adjusts the span of the monitor output. 

Maximum monitor output value (RTH)

This parameter is set to treat any value as 

the maximum output value with respect to 

the input range.

High limit for PV display color change (PCH)

Sets the high limit for PV limit mode or SP 

deviation mode of Active color PV display.

Low limit for PV display color change (PCL)

Sets the low limit for PV limit mode or SP 

deviation mode of Active color PV display.

Minimum monitor output value (RTL)

This parameter is set to treat any value as 

the minimum output value with respect to the 

input range. 

Communication protocol (PSL)

Sets the communication protocol.

Communication address (ADR)

Sets the communication address. 

Baud rate (BPS)

Sets the baud rate. 

Parity (PRI)

Sets the parity.

Stop bit (STP)

Sets the stop bit.

Data length (DLN)

Sets the data length. 

Chapter 8

Chapter 12

Chapter 12

Chapter 11

Burnout action (BSL)

Sets the burnout action.

Wiring resistance correction (WIR)

Used when correcting wiring resistance.

Chapter 8

Chapter 8

Chapter 10

Chapter 10

Chapter 10

Chapter 10

Chapter 10

Section 13.1

Section 13.1

Section 13.1

Section 13.1

Section 13.1

Section 13.1

Section 13.2

Section 13.2

Section 13.2

Section 13.2

Section 13.2

Section 13.2

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 9

Chapter 12

To the Setup Parameter Screen 1

To the Operation Parameter Screen 

Chapter 9

To the Setup Parameter Screen 2

B

is displayed when the monitor output (analog) has been 

specified. 

     is displayed when the 

monitor output (RS-485 

communication) has been 

specified.

The 

symbol indicates a reference chapter/section in this manual.

A

Chapter 11

Chapter 11

         is displayed 

when the monitor 

output (analog) has 

been specified. 

Содержание JUXTA MVRK

Страница 1: ...lly to the socket face Otherwise the terminals may bend and it may cause bad contact The converter shall not tilt 5 degrees or more in either direction when installed When the converter is not connect...

Страница 2: ...5 PART NAMES OF FRONT PANEL AND THEIR FUNCTIONS CAUTION The front panel of the product is constructed to prevent opening Forcing it open will result in breakage 1 PV measured value display Place for a...

Страница 3: ...rm 3 hysteresis HY3 Displayed only for 4 points of alarms Sets the hysteresis of alarm 3 Alarm 4 hysteresis HY4 Displayed only for 4 points of alarms Sets the hysteresis of alarm 4 Alarm ON delay OND...

Страница 4: ...ion describes how to correct wiring resistance when an error occurs due to the influence of the input wiring resistance Correct wiring resistance after completing the wiring 5 4 6 A B B Short circuit...

Страница 5: ...f Adjustment Related Parameters Setup Parameter Screen 2 Parameter Symbol Parameter Name Setting Range Factory Set Value Input adjustment reset RST OFF 0 or ON 1 This parameter is used set to ON to re...

Страница 6: ...ay color mode 6 Press the SET ENT key for more than 3 sec This causes the Operation Parameter Screen to appear Setting the PV display color mode Setup Parameter Screen 2 Continue to the upper right Pr...

Страница 7: ...Press to display RTL Press to display 50 0 Press Press to display RTH Press to display 150 0 Press Press 13 1 4 Adjusting Monitor Output 1 Instruments for adjustment Digital multimeter DMM YOKOGAWA DM...

Страница 8: ...lay 1 Press Press to display PSL Press or to display the communication protocol number to use Press Press Press the DOWN key to display 1 on the DATA display Press the SET ENT key to display the Setup...

Отзывы: