IM 12B06J09-01E-E
16
Appendix 1:
Safety precautions for associated intrinsically safe type
(Model: IB100-CB)
1. Control drawing
Specific Condition of Use:
- This is an accessory device intended for connection to the intrinsically safe apparatus only
when the intrisically safe apparatus is located in a non-hazardous area.
Notes:
- No revision to this drawing without prior approval of FM.
- Warning: Do not either take IB100 into hazardous (classified) location or connect ot to any
equipment located in a hazardous (classified) location
- Warning: Substitution of components may impair intrinsic safty
2. Technical Data
1) US
- Applicable Standards:
FM Class 3600: 2011
FM Class 3610: 2015
FM Class 3810: 2005
ANSI/UL 60079-0: 2013
ANSI/UL 60079-11: 2014
ANSI/ISA 61010-1: 2012
- Ratings and Marking code: Associated apparatus for Class I/II/III, Division 1,
Groups A, B, C, D, E, F, G
Class I, Zone 0, [AEx ia] IIC
2) Canada
- Certificate:
FM16CA0186X
- Applicable Standards:
CAN/CSA-C22.2 No. 0-10: 2010 (R2015)
CAN/CSA-C22.2 No. 60079-0: 2015
CAN/CSA-C22.2 No. 60079-11: 2014
CAN/CSA-C22.2 No. 61010-1: 2012
- Ratings and Marking code: [Ex ia Ga] IIC
Associated apparatus for
Class I/II/III, Division 1,
Groups A, B, C, D, E, F, G
Non-hazardous Area (Unclassified Location)
IS apparatus
Box Assy
Ui (or Vmax) ≥ Uo
Ii (or Imax) ≥ Io
Pi ≥ Po
IB100 Interface Box (Box Assy + Cable Assy)
U0: 5 V
Io: 205 mA
Po: 260 mW
Cable Assy.