1-13
IM 04L57B01-01EN
Overview and Functions
1
2
3
4
5
6
App
1.7 Modbus Register Map
To access the GX70SM as a Modbus slave device, refer to the following register
assignments.
Register assignments of the GX70SM
Data
Register number
Data type Read/Write
Description
Data serial number
40001
UINT32_L
R
Input 1 data
40003
FLOAT_L
Input 2 data
40005
Input 3 data
40007
Humidity data
When the /RH option is installed
Input 1 status
40009
UINT16
Input 2 status
40010
Input 3 status
40011
Humidity status information
When the /RH option is installed
Input status
40012
Device serial number 40013 to 40017
UINT16
UTF-8 string. 2 characters for one
register
Device status
40018
UINT16
RSSI value (dBm)
40019
INT16
Received signal strength on the
coordinator (repeater)
Elapsed time (s)
40020
UINT16
Elapsed time on the coordinator*
* An approximate reference value.
Data type
Symbol
Description
INT16
16-bit signed integer
UINT16
16-bit unsigned integer
UINT32_L
32-bit unsigned integer (little endian)
FLOAT_L
32-bit floating point (little endian)
Structure of the Data Serial Number and Input 1 to 3 Data Registers
Example of input 1 data
Higher word
Lower word
Register 40004
Input 1 data
Register 40003
Structure of the input 1 to 3 status registers
Error code
Meaning
0
No error
1
Skip
2
+Over
3
–Over
4
+Burnout
5
–Burnout
6
A/D error
7
Invalid data
16
Computation error
17
Communication error
5 bits
Status information
0
Reserved area
Error code
RJC error
A/D calibration value error
0 0 0 0 0 0 0 0
2 bytes
Higher
Lower