<8. Maintenance>
8-9
IM 01W03D01-01EN
Integral
indicator
NAMUR
NE107
category
*
1
Bit
Diagnostic
Status
Diagnostic
Status Detail
Cause
Release/
recovery
conditions
(except
restart) *
2
Output
Operation
Action
AL.60
C
24
Out of
service
AI1 OUT OF
SERVICE
AI1 block is
O/S mode
Recover
when the
mode target
of alert block
is other than
O/S
Output value:
Hold previous
value
Output
status: BAD
Configuration
Err
Check the AI1
block setting
AI2 OUT OF
SERVICE
AI2 block is
O/S mode
A Check the
AI2 block
setting
AI3 OUT OF
SERVICE
AI3 block is
O/S mode
Check the AI3
block setting
AI4 OUT OF
SERVICE
AI4 block is
O/S mode
Check the AI4
block setting
AL.61
C
17
Simulation is
active
AI1
SIMULATION
ACTIVE
Simulate
Switch of
AI1 block is
enabled
Recover
when the
Simulate
Switch of
target block is
set to disable
Output
Simulate
Value of AI1
block
Check the AI1
block setting
AI2
SIMULATION
ACTIVE
Simulate
Switch of
AI2 block is
enabled
Output
Simulate
Value of AI2
block
Check the AI2
block setting
AI3
SIMULATION
ACTIVE
Simulate
Switch of
AI3 block is
enabled
Output
Simulate
Value of AI3
block
Check the AI3
block setting
AI4
SIMULATION
ACTIVE
Simulate
Switch of
AI4 block is
enabled
Output
Simulate
Value of AI4
block
Check the AI4
block setting
AL.80
F
8
Connected
device
Failure
HART DEVICE
MALFUCTIONED
Detect
HART Status
Device
Malfunctioned
*
4
Check the
status of the
HART device,
and take
measures
according to
the manual
Output value:
Normal
Output status:
BAD non-
specific
Check the
setting of the
HART device
connected to
the FN310
AL.81
C
7
Connected
device
Function
Check
HART DEVICE
CONFIGURATION
CHANGED
Detect
HART Status
Configuration
Changed*
4
Reset the
Configuration
changed flag
of the HART
device
Normal action Check the
setting of the
HART device
connected to
the FN310
AL.82
HART DEVICE
COLD START
Detect HART
Status Cold
Start*
4
Check the
status of the
HART device,
and take
measures
according to
the manual
Normal action Check the
setting of the
HART device
connected to
the FN310
AL.83
HART DEVICE
MORE STATUS
AVAILABLE
Detect
HART Status
More Status
Available*
4
Normal action Check the
setting of the
HART device
connected to
the FN310
AL.84
HART DEVICE
LOOP
CURRENT
FIXED
Detect
HART Status
Loop Current
Fixed*
4
Output value:
Normal
Output status:
Uncertain
substituted or
manual Entry
Check the
setting of
FN310