10.  GENERAL SPECIFICATIONS

10.2 MODEL AND SUFFIX CODES

MODEL AND SUFFIX CODES

Model

Description

Suffix Codes

T1009E.EPS

Cast alluminum alloy

Vertical piping, left side high pressure, and process connection downside 

Horizontal piping and right side high pressure 

Horizontal piping and left side high pressure

Bottom Process Connection, left side high pressure

Digital indicator 

None

ASTM-B7M carbon steel 

316 SST (ISO A4-70) stainless steel 

ASTM grade 660 stainless steel

304 SST  2-inch pipe mounting, flat type (for horizontal piping)  

304 SST  2-inch pipe mounting, L type (for vertical piping) 

304 SST  2-inch pipe mounting (for bottom process connection type)

None

1/2NPT female, two electrical connections (One connection for RTD)

M20 female, two electrical connections (One connection for RTD)

1/2NPT female, two electrical connections and a blind plug 

*2

M20 female, two electrical connections and a blind plug 

*2

Multivariable transmitter

without process connector (Rc1/4 female on the cover flanges) 

with Rc1/4 female process connector 

with Rc1/2 female process connector 

with 1/4 NPT female process connector 

with 1/2 NPT female process connector 

without process connector (1/4 NPT female on the cover flanges)

4 to 20 mA DC with digital communication (HART protocol)

Digital Communication (FOUNDATION Fieldbus protocol. refer to IM01C25R03-01E)

Refer to Table 7.

0.5 to 100 kPa 

(2 to 400 inH

2

O) 

2.5 to 500 kPa 

(10 to 2000 inH

2

O)

Electrical connection

Bolts and nuts material

Installation

Integral indicator

Mounting bracket

Fixed temperature (without cable) 

*5

RTD input with 0.5 m (1.64 ft) of shielded cable and two cable glands

RTD input with 4 m (13.1 ft) of shielded cable and two cable glands

RTD input with 7.5 m (24.6 ft) of shielded cable and two cable glands

RTD input with 25 m (81 ft) of shielded cable and two cable glands 

*6

RTD input with 4 m (13.1 ft) of shielded cable without cable gland 

*4

RTD input with 7.5 m (24.6 ft) of shielded cable without cable gland 

*4

RTD input with 25 m (81 ft) of shielded cable without cable gland 

*4

External temperature input  

*3

Multi Sensing (DP, P and T)

Mass Flow Measurement (Flow, DP, P and T)

Measurement function

Amplifier housing

EJX910A

Output signal

Wetted parts 
material

 *1

Process connections

Measurement 
span (Capsule)

Option codes

/

  Optional specification

 · · · · · · · · · · · · · · · · · · · · · · · · · 

-E · · · · · · · · · · · · · · · · · · · · · · ·

-F · · · · · · · · · · · · · · · · · · · · · · ·

M · · · · · · · · · · · · · · · · · · · · · 

H · · · · · · · · · · · · · · · · · · · · · 

0 · · · · · · · · · · · · · · · · · · 

1 · · · · · · · · · · · · · · · · · · 

2 · · · · · · · · · · · · · · · · · · 

3 · · · · · · · · · · · · · · · · · · 

4 · · · · · · · · · · · · · · · · · · 

5 · · · · · · · · · · · · · · · · · · 

J · · · · · · · · · · · · · · · · 

G · · · · · · · · · · · · · · · ·

C · · · · · · · · · · · · · · · ·

-7 · · · · · · · · · · · · · · 

-8 · · · · · · · · · · · · · · 

-9 · · · · · · · · · · · · · ·  

-B · · · · · · · · · · · · · · 

1 · · · · · · · · · · · · 

2 · · · · · · · · · · · 

4 · · · · · · · · · · · 

7 · · · · · · · · · · · 

9 · · · · · · · · · · · 

D · · · · · · · · 

N · · · · · · · ·

B  · · · · · 

D  · · · · ·  

G  · · · · · 

N  · · · · · 

-0  · · ·  

-1  · · ·   

-2  · · · 

-3  · · ·  

-4  · · ·   

-B  · · ·  

-C  · · ·   

-D  · · · 

A  · ·

B  · · 

S   · · · · · · · · · · · · · · · · · · · 

The “

” marks indicate the most typical selection for each specification.

*1:

Users must consider the characteristics of selected wetted parts material and influence of process fluids. Specifying
inappropriate materials has the potential to cause serious damage to human body and plant facilities resulted from an
unexpected leak of the corrosive process fluids.

*2:

For External Temperature Input code 0 (Fixed temperature) .

*3:

Recommended External Temperature Input Cable is as shown in Table 6. RTD is not provided.

*4:

Specify when using conduit for RTD connection.

*5:

Preset external temperature value is used for density compensation.

*6:

Not applicable for output signal code -F and option code /KS2.

Содержание DpharpEJX vigilantplant EJX910A

Страница 1: ...User s Manual Y okogawa Electric Corporation EJX910A Multivariable Transmitters IM 01C25R01 01E IM 01C25R01 01E 2nd Edition...

Страница 2: ...ns Check 3 1 3 2 Unpacking 3 1 3 3 Storage 3 1 3 4 Selecting the Installation Location 3 2 3 5 Pressure Connection 3 2 3 6 Waterproofing of Cable Conduit Connections 3 2 3 7 Restrictions on Use of Rad...

Страница 3: ...ecting Shielded Cable with Cable Gland External temperature input code 1 2 3 and 4 7 3 7 6 2 Connecting Shielded Cable for Conduit Use External temperature input code B C and D 7 5 7 6 3 Removing Shie...

Страница 4: ...l Indicator 9 4 9 4 2 Replacing the CPU Board Assembly 9 5 9 4 3 Cleaning and Replacing the Capsule Assembly 9 5 9 4 4 Replacing the Process Connector Gaskets 9 7 9 5 Troubleshooting 9 7 9 5 1 Basic T...

Страница 5: ...this manual are limited to those for the standard type under the specified model number break down and do not cover custom made instruments Please note that changes in the specifications construction...

Страница 6: ...ician who has an expert knowledge of this device Operators are not allowed to carry out installation unless they meet this condition With high process temperatures care must be taken not to burn yours...

Страница 7: ...contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa office If a problem arises with this instrument please inform us of the nature of the problem and...

Страница 8: ...Neem indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger SF Kaikkien ATEX Ex...

Страница 9: ...surement instruments can calculate and output the flow value using these three measured variables The EJXMVTool mass flow configuration software is used to configure mass flow calculation Simultaneous...

Страница 10: ...Location Flow Configure Bench Connect Power Supply Connect Personal Computer Perform Configuration Tasks see Chapter2 Review Installation Considerations see Chapter5 Mount Transmitter see Chapter5 Pe...

Страница 11: ...alue with a high level of accuracy The flow factors that are automati cally compensated are discharge coefficient diameter of primary device upstream internal pipe diameter gas expansion factor densit...

Страница 12: ...sired flow is obtained 7 Remove the HART modem from the EJX910A 8 Turn off the power supply NOTE 1 Refer to the following instruction manuals for a more detailed explanation When setting with the HART...

Страница 13: ...d Table 2 4 Normal Standard Volume Flow Unit HART protocol type T0204E EPS Unit LCD Communication normal cubic meter per hour Nm3 h normal liter per hour NL h Standard cubic feet per minute SCFM Tabl...

Страница 14: ...ameters 1 Selection of the flow equation Select the desired operational expression according to the fluid type and the flow unit category shown in Table 2 1 2 Confirming the unit The unit to be used i...

Страница 15: ...unit of use Differential pressure unit of use Pa Example 2 Calculation of Kfactor When Qm unit kg s Differential pressure unit kPa Kfactor 4 Nc C 1 4 d2 2 b 1 K 0 7853982 31 62278 0 6043 1 0 1296 0 9...

Страница 16: ...lected at 1 5 Downloading flow parameter to transmitter Input Kfactor Tb SPb and TempK1 liquid to the transmitter by a communication tool or EJXMVTool IMPORTANT If either the setting of flow unit or d...

Страница 17: ...pecifications are written on the name plate attached to the case F0302E EPS Figure 3 2 Name Plate 3 2 Unpacking Keep the transmitter in its original packaging to prevent it from being damaged during s...

Страница 18: ...g precautions must be observed in order to safely operate the transmitter under pressure a Make sure that all the process connector bolts are tightened firmly b Make sure that there are no leaks in th...

Страница 19: ...or FOUNDATION Filedbus explosion protedted type please refer to IM 01C25R03 01E If a customer makes a repair or modification to an intrinsically safe or explosionproof instrument and the instrument is...

Страница 20: ...tion wiring shall be in conduit as shown in the figure WARNING A SEAL SHALL BE INSTALLED WITHIN 50cm OF THE ENCLOSURE UN SCELLEMENT DOIT TRE INSTALL MOINS DE 50cm DU BO TIER WARNING WHEN INSTALLED IN...

Страница 21: ...sive atmospheres No KEMA 06ATEX0037 X Applicable Standard EN 50014 EN 50020 EN 50284 EN 50281 1 1 Type of Protection and Marking code EEx ia IIC T4 Group II Category 1G 1D Ambient Temperature for gas...

Страница 22: ...a resistor R such that Imaxout Uz R The safety barrier shall be certified by notify body EU as ATEX When using non isolation barrier connect 1 to IS earthing system Note 2 RTD sensor is prepared by t...

Страница 23: ...conduits or use shielded twisted pair cabling when installing EJX series transmitters in a plant 3 11 Pressure Equipment Directive PED 1 General EJX series pressure transmitters are categorized as pr...

Страница 24: ...oor atmosphere Normally only non conductive pollution occurs Occasionally however temporary conductivity caused by condenstaion must be expected 2 Installation Category I Overvoltage category Installa...

Страница 25: ...tion Note 2 Note 1 See subsection 10 2 Model and Suffix Codes for details Note 2 Applicable for HART communication type Set the switches as shown in the figure above to set the burn out direction and...

Страница 26: ...nce between the impulse piping connection ports is usually 54 mm figure 5 1 By changing the orientation of the process connector the dimension can be changed to 51 mm or 57 mm The transmitter can be m...

Страница 27: ...ust be repositioned To reposition a drain vent plug use a wrench to slowly and gently unscrew it Then remove and remount it on the opposite side Wrap sealing tape around the drain vent plug threads 1...

Страница 28: ...in vent plugs to the opposite side as described in subsection 4 3 F0505E EPS Process connector Setscrew Before After rotating 180 Figure 5 5 Before and After Modification 5 4 2 Using the Communicator...

Страница 29: ...on more than the above limit F0507E EPS Vertical impulse piping type Horizontal impulse piping type Pressure detector section Transmitter section Rotate 0 to 180 segments Rotate 0 to 180 segments Tran...

Страница 30: ...ounting bolts uniformly 4 Removing the Impulse Piping Connecting Port Dustproof Cap The impulse piping connecting port on the transmitter is covered with a plastic cap to keep out dust This cap must b...

Страница 31: ...ter and 3 valve manifold be sure to CLOSE the low pressure and high pressure stop valves OPEN the equalizing valve and leave the manifold with the equalizing valve OPEN You must do this in order to a...

Страница 32: ...s no temperature difference between them 5 Condensate Pots for Steam Flow Measure ment If the liquid in the impulse piping repeatedly condenses or vaporizes as a result of changes in the ambient or pr...

Страница 33: ...front The transmitter impulse piping connection is shown for a vertical impulse piping connection configura tion in which the direction of connection is either upwards or downwards If the impulse lin...

Страница 34: ...ded wires in areas that are susceptible to electrical noise c In areas with higher or lower ambient temperatures use appropriate wires or cables d In environment where oils solvents corrosive gases or...

Страница 35: ...4 Check Meter Connection Connect the check meter to the CHECK and _termi nals Use hooks A 4 to 20 mA DC output signal from the CHECK and _ terminals Note Use a check meter whose internal resistance is...

Страница 36: ...proof packing adapter or use a flameproof metal conduit Wiring cable through flameproof packing adapter Apply a non hardening sealant to the terminal box connection port and to the threads on the flam...

Страница 37: ...or the RTD electrical connection F0716E EPS Entry with Seal 1 2NPT Type M20 Type Running Coupler Gasket Entry with Seal Backnut Running Coupler Backnut CAUTION Input output signal is non isolated Do n...

Страница 38: ...e transmitter s terminal box 3 Insert the cable through the conduit and attach it to the RTD electrical connection CAUTION Do not pull the cable or subject it to excessive mechanical shock 7 6 3 Remov...

Страница 39: ...de RTD Terminal T0701E EPS RTD Terminal B A 2 Wire 3 Wire 4 Wire White White White a open b Blue2 Blue2 Blue1 and Blue2 Blue1 Blue1 NOTE The color display in the table shows the white line of the cabl...

Страница 40: ...For the shielded cables in this example of flowmeter installation use two wire separately shielded cables This supply voltage requires a power sourse with a maximum output current of no less than E R...

Страница 41: ...eck that there are no liquid leaks in the impulse piping 3 valve manifold transmitter or other components Venting Gas from the Transmitter Pressure detector Section Since the piping in the example of...

Страница 42: ...ocedure for the zero adjustment screw For the communicator procedure see the communication manual IMPORTANT Do not turn off the power to the transmitter immediately after performing a zero point adjus...

Страница 43: ...tained resistance as the input value then deliver it to the transmitter by means of a variable resistor Measure the resulting output signal with the voltmeter digital multimeter and check the output v...

Страница 44: ...drain vent screw on the transmitter to completely drain vent any stagnated liquid gas However since draining condensate or bleeding off gas disturbs the pressure measurement this should not be done wh...

Страница 45: ...libration Instruments Se lection Table 9 1 lists the instruments that can be used to calibrate a transmitter When selecting an instrument consider the required accuracy level Exercise care when handli...

Страница 46: ...ge close to that of the transmitter T0901E EPS for 0 to 10 kPa for 10 to 0 kPa for 25 to 130 kPa for 0 to 25 kPa for 80 to 0 kPa for 100 to 700 kPa for 0 to 100 kPa for 80 to 0 kPa for 0 to 3000 kPa f...

Страница 47: ...igure 9 1 Instrument Connections for Differential Pressure HART protocol type V R Rc P Using pressure generator Reference pressure High pressure side High pressure side Low pressure side open to atmos...

Страница 48: ...the cover can be opened When a cover is closed it should be locked by a shrouding bolt without fail Tighten the shroud ing bolt to a torque of 0 7 N m Shrouding Bolt Shrouding Bolt F0903E EPS Figure...

Страница 49: ...ll the CPU assembly straight forward to remove it 6 Disconnect the flat cable cable with white connec tor at the end that connects the CPU assembly and the capsule NOTE Be careful not to apply excessi...

Страница 50: ...two setscrews that connect the transmitter section and pressure detector section 3 Remove the hexagon head screw and the stopper 4 Separate the transmitter section and pressure detector section 5 Remo...

Страница 51: ...ersonnel 9 5 1 Basic Troubleshooting First determine whether the process variable is actually abnormal or a problem exists in the measurement system If the problem is in the measurement system isolate...

Страница 52: ...transmitter loop wiring Do the loop numbers match YES NO YES NO NO YES NO NO YES YES YES NO YES Check the sensor connection and correct it Is the sensor correctly connected NO Refer to error message s...

Страница 53: ...ected Check the sensor connection and correct it Connect a communicator and check self diagnostics Contact Yokogawa service personnel F0911E EPS Are valves opened or closed correctly Is impulse piping...

Страница 54: ...to operate and output Continues to operate and output AL 12 CAP TMP CT outside limit Capsule temperature is outside range 50 to 130 C AL 13 AMP TMP AT outside limit Amplifier temperature is outside ra...

Страница 55: ...isted immediately before the error occurred Continues to operate and output AL 55 SP ADJ SP SPAN trim err SP ZERO trim err Check settings and change them as needed Check Simulation Mode Leave from Tem...

Страница 56: ...0 to 850 273 to 1927 L M H Span Range Fixed Temperature K F C Measurement External Temperature Span Range FUNCTIONAL SPECIFICATIONS Output Dual output Both analog and pulse contact output can be obtai...

Страница 57: ...m value In Auto mode mass flow can be measured with high accuracy The flow factors that are automatically compensated are discharge coefficient diameter of primary device upstream internal pipe diamet...

Страница 58: ...gital communication Communication Requirements Safety approvals may affect electrical require ments HART Communication Distance Up to1 5 km 1 mile when using multiple twisted pair cables Communication...

Страница 59: ...Cable gland Nickel plating brass Weight 2 7 kg 6 0 lb without integral indicator mounting bracket process connector and RTD cable Connections Refer to MODEL AND SUFFIX CODE Related Instruments Power D...

Страница 60: ...Electrical connection Bolts and nuts material Installation Integral indicator Mounting bracket Fixed temperature without cable 5 RTD input with 0 5 m 1 64 ft of shielded cable and two cable glands RT...

Страница 61: ...tandards Association CSA 1 Code 4 is not applicable Table 10 5 Wetted Parts Materials Cover flange and process connector ASTM CF 8M 1 Capsule gasket Teflon coated 316L SST Drain Vent plug 316 SST Caps...

Страница 62: ...o 60 C Tp 100 C T120 C Tamb 40 to 60 C Tp 120 C Combined FF1 and FS1 CSA Explosionproof Approval 1 For CSA C22 2 Explosion proof for Class I Groups B C and D Dustignition proof for Class II III Groups...

Страница 63: ...1000 A 1 40 s 100 times Applicable Standards IEC 61000 4 4 IEC 61000 4 5 Amplifier cover and terminal cover Munsell 7 5 R4 14 PR NAMUR NE43 Compliant Output signal limits 3 8 mA to 20 5 mA Failure ala...

Страница 64: ...88 47 1 85 Integral Indicator optional Conduit connection for RTD for flame proof type Shrouding bolt Drain plug Low pressure side Vent plug High pressure side Ground terminal Zero adjustment 117 3 4...

Страница 65: ...optional 95 3 74 221 8 70 79 3 11 Conduit connection For RTD 2 inch pipe O D 60 5 mm Integral indicator optional Shrouding bolt for flame proof type Unit mm approx inch Bottom Process Connection Type...

Страница 66: ...t cable 3 5 3 9 3 Add CENELEC ATEX intrinsically safe type 3 6 3 10 Correct errors 3 11 Revise information for PED 3 12 Section added 7 1 7 1 Add note for fieldbus type in IMPORTANT notice 7 3 7 5 1 A...

Отзывы: