<8. Parameter Summary>
30
IM 01C22A01-01E
BRAIN Communication Parameter List
Instruments to which applicable:
F: Differential pressure transmitters:
EJA110A, EJA120A, EJA130A, EJA118W, EJA118N, EJA118Y, and EJA115
P: Pressure transmitters:
EJA310A, EJA430A, EJA440A, EJA510A, EJA530A, EJA438W, and EJA438N
L: Liquid level transmitters:
EJA210A and EJA220A
No.
Item
Description
Rewrita-
bility
Remarks
Default Value
Applicability
F
P
L
01 MODEL
Model+capsule type
—
02 TAG NO.
Tag number
—
16 alphanumerics
03 SELF CHECK
Self-diagnostic result
—
GOOD/ERROR
A
DISPLAY
Measured data display
—
Menu name
A10 OUTPUT (%)
Output (in %)
—
–5 to 110%*
3
A11 ENGR. OUTPUT
Output (in engineering
units)
—
–19999 to 19999
A20 AMP TEMP
Amplifier temperature
—
Unit specified in D30
A21 CAPSULE TEMP
Capsule temperature
—
Unit specified in D30
A30 STATIC PRESS
Static pressure
—
Unit specified in D31*
1
—
A40 INPUT
Input (indicated as the
value after zeroing)
—
–32000 to 32000
A60 SELF CHECK
Self-diagnostic
messages
—
See Chapter 7
B
SENSOR TYPE
Sensor type
—
Menu name
B10 MODEL
Model+span
—
16 uppercase alphanumerics
B11 STYLE NO.
Style number
—
B20 LRL
Lower range-limit
—
–32000 to 32000
B21 URL
Upper range-limit
—
–32000 to 32000
B30 MIN SPAN
Minimum span
—
–32000 to 32000
B40 MAX STAT.P.
Maximum static pressure*
4
—
—
B60 SELF CHECK
Self-diagnostic
messages
—
Same as A60
C
SETTING
Setting data
—
Menu name
C10 TAG. NO.
Tag number
16 alphanumerics
As specified when
ordered.
C20 PRESS UNIT
Measurement range units
Selected from mmH
2
O,
mmAq,
mmWG, mmHg,
Torr, Pa, hPa, kPa,
MPa,
mbar, bar, gf/cm
2
, kgf/cm
2
,
inH
2
O, inHg, ftH
2
O, psi, or
atm
As specified when
ordered.
C21 LOW RANGE
Measurement range, lower
range value
–32000 to 32000(but within
measurement range)
As specified when
ordered.
C22 HIGH RANGE
Measurement range,
higher range value
–32000 to 32000(but within
measurement range)
As specified when
ordered.
C30 AMP DAMPING
Damping time constant
Selected from 0.2*
2
, 0.5, 1.0,
2.0, 4.0, 8.0, 16.0, 32.0, or
64.0 sec.
2.0 s
C40 OUTPUT MODE
Output mode and integral
indicator mode
Selected from OUT:LIN; DSP:
LIN, OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
As specified when
ordered.
If not specified,
OUT: LIN; DSP: LIN.
—
—
C60 SELF CHECK
Self-diagnostic messages
—
Same as A60
D
AUX SET 1
Auxiliary setting data 1
—
Menu name
D10 LOW CUT
Low cut
0.0 to 20.0%
10.0%
D11 LOW CUT MODE Low cut mode
LINEAR/ZERO
LINEAR
D20 DISP SELECT
Display selection
NORMAL %/USER SET,
USER & %/INP PRES, PRES
& %
As specified when
ordered.
D21 DISP UNIT
Engineering unit for display
8 uppercase alphanumerics
D22 DISP LRV
Engineering range, lower
range value
–19999 to 19999
As specified when
ordered.