IM 01C25F01-01E
6-2
6. WIRING
6.3.4 Check Meter Connection
Available only when /AL is not specified.
Connect the check meter to the CHECK + and –
terminals. (Use hooks.)
• A 4 to 20 mA DC output signal from the CHECK +
and – terminals.
(Note) Use a check meter whose internal resistance is 10
Ω
or less.
SUPP
LY
PU
LS
E
CHEC
K
ALAR
M
Transmitter terminal box
F0604.EPS
Power supply
–
+
Check meter
Figure 6.4 Check Meter Connection
6.3.5 Status Output Connection
When option code /AL is specified, connect the
external wiring as shown in Figure 6.5.
To configure and activate the process alarm function
and status output, it is necessary to set some param-
eters. Refer to each communication manual for
procedures.
SUPP
LY
PU
LS
E
CHEC
K
ALAR
M
Transmitter
terminal box
Magnetic
valve
AC power supply
External power
supply 30V DC,
120mA max
+
–
250
Ω
24V DC
Use two-wire separately shielded cables.
Distributor
Shielded cable
F0605.EPS
Figure 6.5
Status Output Connection
6.4 Wiring
6.4.1 Loop Configuration
Since the DPharp uses a two-wire transmission system,
signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The
transmitter and distributor are connected as shown
below.
For details of the power supply voltage and load
resistance, see section 6.6; for communications line
requirements, see section 9.1.
(1) General-use Type and Flameproof Type
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
F0606.EPS
SUPP
LY
PULS
E
CHEC
K
ALARM
Figure 6.6
Connection between Transmitter and
Distributor
(2) Intrinsically Safe Type
With the intrinsically safe type, a safety barrier must be
included in the loop.
Hazardous Location
Nonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
Receiver
instrument
Safety barrier
F0607.EPS
SUP
PLY
PULSE
CHEC
K
ALARM
Figure 6.7
Connection between Transmitter and
Distributor
6.4.2 Wiring Installation
(1) General-use Type and Intrinsically Safe
Type
With the cable wiring, use a metallic conduit or
waterproof glands.
• Apply a non-hardening sealant to the terminal box
connection port and to the threads on the flexible
metal conduit for waterproofing.
F0608.EPS
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads for
waterproofing.
Figure 6.8 Typical Wiring Using Flexible Metal Conduit