3. COMPONENT NAMES
3.
COMPONENT NAMES
HIGH
LOW
BO H
L
WR E
D
H
L
E
D
H
L
E
D
F0301.EPS
H
L
E
D
H
L
E
D
YES
(Write disabled)
NO
(Write enabled)
Slide switch
(Note 2)
Integral
indicator
(Note 1)
Mounting screw
Amplifier Cover
Cover flange
Process connector
(Note 1)
Process connection
(low pressure side)
Zero-adjustment screw
Conduit
connection
External indicator
conduit connection
(Note 1)
CPU assembly
Range-setting
switch
(Note 1)
(See Subsection 7.6)
Burnout direction switch
Write protection switch
Burnout direction switch (BO)
Hardware write protection switch (WR)
Burnout Direction
Switch Position
Burnout Direction
Write Protection
Switch Position
Write Protection
Transmitter section
Bolt
(Note 2)
(Note 2)
Note 1: See subsection 9.2, “Model and Suffix Codes,” for details.
Note 2: Set the switches as shown in the figure above to set the burn-out direction and write protection. The Burnout switch is set to
the H side for delivery (unless option code /C1 or /C2 is specified in the order), and the hardware write protection switch is set
to E side.
The setting of the switches can be confirmed via communication. An external zero adjustment screw can only be disabled by
communication. To disable the screw, set a parameter before activating the hardware write pretect function.See each
communication manual for details.
Figure 3.1 Component Names
Table 3.1 Display Symbol
Display Symbol
Meaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
T0301.EPS
Write protect function is enabled.