IM CL155
13
Peak Current (10ms)
Range
Measuring range
Accuracy (Frequency Range)
400A
0 to 400.0A
±
3.0% rdg
±
6dgt (50/60Hz)
±
3.0% rdg
±
10dgt (40 to 1kHz)
2000A
0 to 1500A
±
4.0% rdg
±
6dgt (50/60Hz)
±
4.0% rdg
±
10dgt (40 to 1kHz)
1500 to 2000A
±
4.5% rdg (50/60Hz)
OUTPUT (AC Current Ranges)
DC Output : 100.0mV per 1000 counts (Output impedance : about 10k
Ω
)
Range
Measuring range
Accuracy (Frequency Range)
400A
0 to 400.0mV/0 to 400A
±
1.5% rdg
±
0.5mV (50/60Hz) *1
±
2.5% rdg
±
0.5mV (40 to 1kHz)
2000A
0 to 150.0mV/0 to 1500A
±
1.5% rdg
±
0.5mV (50/60Hz) *1
±
3.5% rdg
±
0.5mV (40 to 1kHz)
150.0 to 200.0mV/1500 to 2000A
±
3.5% rdg (50/60Hz)
*1 : 400A range : 5 to 100% of range , 2000A range : 200A to 2000A
■General Specifications
●
Operating System : Dual integration
●
Measurement Function : AC current, DC current, AC voltage, resistance,
continuity check
●
Display : Liquid crystal display with maximum counts of 3999
●
Overrange Indication : "OL" is shown on the display
●
Response Time : Approx. 2 seconds.
●
Temperature and Humidity for Guaranteed Accuracy : 23
℃
±
5
℃
, relative
humidity 45 to 75% without condensation
●
Operating Temperature and Humidity : 0 to 40
℃
, relative humidity up to 85%
without condensation
●
Storage Temperature and Humidity : -20 to 60
℃
, relative humidity up to 85%
without condensation
●
Effect of conductor position : At every part inside the jaws
Range
Measuring range Conductor size
Effect of conductor position
400A
0 to 400A
φ
10mm or less
±
2.0%rdg
±
3dgt
2000A
0 to 1500A
φ
25mm or less
±
2.0%rdg
±
3dgt
1500 to 2000A
φ
25mm or less
±
5.0%rdg
●
Effect of external magnetic field : 1A or less in AC or DC magnetic field of
400 A/m