General

Specifications

<<Contents>>  <<Index>>

n

 GENERAL

The Optical ESB Bus Repeater Module converts the ESB bus to an optical signal and transmits it. The ESB bus 
transmission distance can be extended within the range of up to 4 km by connecting the ANT421 Optical ESB Bus 

Repeater Master Module and ANT522 Optical ESB Bus Repeater Slave Module with an optical fiber cable.

These modules can replace existing ER bus and RIO bus to the optical ESB bus by utilizing the existing multimode 

fiber cables.

l

 ANT421 Optical ESB Bus Repeater Master Module for 4 km

This module can be installed in the Field Control Unit, FIO Node Unit (ESB Bus Node Unit,Optical ESB Bus Node 

Unit) and Optical ESB Bus Repeater Unit.
To connect ANT421 to ESB Bus, ANT401 requires the ESB Bus Adapter “Connector unit for ESB Bus” (A2EE2A-N).
To terminate ESB Bus at ANT421, ANT421 requires the ESB Bus Adapter “Connector unit with terminator for ESB 

Bus” (A2EE2A-T). ESB Bus Adapter A2EE2A should be ordered separately.

l

 ANT522 Optical ESB Bus Repeater Slave Module for 4 km

ANT522 is installed as standard in Optical ESB Bus Node Unit as a slave module of the optical ESB bus. It can also 

be installed in Optical ESB Bus Repeater Unit. 
To connect ANT522 to ESB Bus, ANT522 requires the ESB Bus Adapter “Connector unit for ESB Bus” (A2EE3A-N

).

To terminate ESB Bus at ANT522, ANT522 requires the ESB Bus Adapter “Connector unit with terminator for ESB 

Bus” (A2EE3A-T

).

To monitor the temperatures and fans in the cabinet, specify “With HKU interface” (A2EE3A-

H).

The ESB Bus Adapter A2EE3A should be ordered separately.

l

 Installation Position

The following table shows the units and numbers of slots in which ANT421 and ANT522 can be installed.
For the installation positions corresponding to the slot numbers, see “FIO System Overview” (GS 33J60A10-01EN), 

“N-IO System Overview” (GS 33J62A10-01EN), and “Field Control Unit, Cabinet Utility Kit (for RIO System Upgrade)” 

(GS 33J64E10-01EN).

Table  ANT421 Optical ESB Bus Repeater Master Module for 4 km

Installable Unit and Slot Number

FCU

Base Plate (for FCU)

FIO Node Unit

Base Plate (for FIO)

Optical ESB Bus 

Repeater Unit

Base Plate (for FIO)

AFV30

,

 

AFV40

, A2FV50

A2FV70

, A2BE1D

ANB10

, ANB11

, A2BE2D 

(*3)

ANT10U, A2BE2D (*3)

Single configuration (*1)

IO1, 3, 5

IO1, 3, 5, 7

IO1, 3, 5, 7, B1

Dual-redundant configuration (*2)

IO1 to 6

IO1 to 8

IO1 to 8, B1, 2

*1: 

A dummy cover is to be attached to the even-numbered slot of a pair of slots in which the module is installed. 

*2: 

Install the module in the slots with the following numbers: IO1-2, IO3-4, IO5-6, IO7-8, and B1-2

*3:   Base plate A2BE2D constitutes FIO node unit (ESB Bus Node Unit, Optical ESB Bus Node Unit) or Optical ESB bus 

repeater unit with each function modules. Refer to “A2BE2D Base Plate (for FIO)” (GS 33J60G30-01EN) for detail.

ANT421, ANT522, A2EE2A , A2EE3A 

Optical ESB Bus Repeater 

Module for 4 km (for N-IO/FIO Multimode Fiber)

ESB Bus Adapter(for ANT4

1)

ESB Bus Adapter(for ANT5

2)

Yokogawa Electric Corporation

2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

GS 33J60F55-01EN

GS 33J60F55-01EN

©Copyright Feb. 2015 (YK)

7th Edition Dec. 3, 2021 (YK)

[Release 6]

Содержание Centum ANT421

Страница 1: ...the temperatures and fans in the cabinet specify With HKU interface A2EE3A H The ESB Bus Adapter A2EE3A should be ordered separately l Installation Position The following table shows the units and num...

Страница 2: ...connection FCU for N IO 16 hops for chain and star connection 2 FCU for RIO System Upgrade 8 hops for chain and star connection Maximum transmission distance 3 4 km one hop Optical connector type LC...

Страница 3: ...iber cable specifications Maximum permissible optical loss 0 to 7 dB 1 3 m 1 Optical Fiber Type Quartz multimode fiber GI 50 125 2 GI 62 5 125 3 Transmission bandwidth Up to 2 km transmission distance...

Страница 4: ...129 130 Unit mm F02E ai A2EE2A N Connector unit for ESB Bus A2EE2A T Connector unit with terminator for ESB Bus IN OUT OPT CN2 CN1 IN OUT OPT CN1 Nominal tolerances Nominal tolerance is 0 8 mm for the...

Страница 5: ...side ANT522 as described below ANT421 for master side and ANT522 for slave side ANT421 for master side and A2EN501 for slave side A2EN501 for master side and ANT522 for slave side Dual redundant modu...

Страница 6: ...4 km or less Optical ESB Bus Node Unit for dual redundant Optical ESB Bus A L F 1 1 1 A L F 1 1 1 A L R 1 2 1 A L R 1 2 1 A N T 5 2 2 A N T 5 2 2 Optical ESB Bus Node Unit for dual redundant Optical...

Страница 7: ...tic cable 4 km Total Max length of Fiber optic cable 8 km Optical ESB Bus Node Unit Optical ESB Bus Node Unit FCU for FIO I O M I O M I O M I O M I O M I O M I O M I O M P S U P S U I O M I O M I O M...

Страница 8: ...P S U E C 4 0 1 E C 4 0 1 C P 4 6 1 or C P 4 7 1 C P 4 6 1 or C P 4 7 1 1 1 Optical ESB Bus Repeater Unit P S U P S U A N T 4 1 1 A N T 4 1 1 A N T 4 0 1 A N T 4 0 1 Optical ESB Bus Node Unit I O M I...

Страница 9: ...Optical ESB Bus Repeater Slave Module for Multimode Fiber Description Model ANT522 Optical ESB Bus Repeater Slave Module 4 km for Multimode Fiber Suffix Codes 5 Standard type with no explosion protec...

Страница 10: ...t to be installed needs to be specified 4 Select the option code ATDOC to follow the ATEX Directive and UKEX Regulation for use in potentially explosive atmospheres Node Unit for Dual Redundant ESB Bu...

Страница 11: ...ew GS 33J01A10 01EN n ORDERING INFORMATION Specify the model and suffix codes and option codes when ordering For selecting the right products for explosion protection please refer to TI 33J01J30 01EN...

Отзывы: