UNIT FEATURES 

 

Automatic 3-minute Compressor Lockout

 

After the compressor cycles off, it will not restart for three minutes. 

 

Random Restart Delay 

To help eliminate power surges after a power outage, the unit is 
equipped with a two to four minute random restart delay feature. 
Whenever the unit is plugged in with the master switch turned on 
and the mode switch set in the cool or heat mode, a random 
restart will occur. A random restart condition can be avoided by 
setting the mode switch in the fan only or off position before 
applying power to the unit. 

 

Indication LEDs

 

The control panel has LEDs that correspond to fan operation and indicate unit status. 

 

High Temperature Protection in Outside

 

In COOL mode the unit will shut off compressor automatically when it detects the outdoor condenser 
temperature is too high to continue operating. After the temperature decreases to a safe level, the unit will 
restart. If this failure occurs 4 times within an hour, the control panel will show the error code-E9. 

 

Failure Tolerance 

If the unit in protection mode has less than 4 times in one hour, the accumulation times will reset to avoid 
system failure. If the unit enters protection mode 4 times in one hour, the system not restart automatically 
and need manually restart. 

 

Weather-Protected Electrical Components

 

Vital electrical components are protected from the elements on the indoor side of the weather barrier. 

 

Highly Featured Microprocessor Controls

 

Microprocessor controls are programmed to interface with the temperature sensors to maximize comfort 
conditions for the room occupant and provide outstanding features. Thermistors are used to sense small 
changes in temperature and allow the microprocessor to monitor and react to changing conditions.

 

 

Automatic Emergency Heat on Heat Pump Units

 

Automatically use electric resistance heat if the heat pump fails. 

 

High-Temperature Heat Pump Operation Protection

 

Automatically protects the compressor if heat pump is operated with high indoor coil temperatures.

 

Power 

to the outdoor fan and the compressor are turned off if the indoor coil gets too hot during heat pump 
operation, to prevent damaging the compressor. 

 

 Fan Motors Permanently Lubricated

 

All units have two fan motors for maximum operating efficiency. Motors are permanently lubricated and 
totally enclosed to reduce maintenance to keep dirt and water out of the motor windings. 

 

 Indoor Fan Speed Selections AUTO/LOW/MEDIUM/HIGH

 

Unit may be operated in low, medium or high fan speed. Select AUTO and the unit will choose the best 
running speed. 

 

Outdoor Two Fan Speed LOW/HIGH

 

Unit detects outdoor condenser coil temperature. During the night when outdoor ambient temperature 
drops, the outdoor fan may auto switch to LOW fan speed to lower the noise for better sleeping. 

 

Rotary Compressor

 

Smoother operation for quiet, dependable service and high efficiency. 

 

Energy saver 

In COOL or HEAT mode, when the compressor shuts down for over 15s, 
the indoor fan will shut down to save energy. 

 

Ls Control 

(

Front

-

Desk Control)

 

The unit can be turned ON/OFF by front desk control switch. This 
function interface is located on the 24V thermostat connection board. 

 

24V General Thermostat interface (optional)

 

This unit is designed to allow the easy installation of a 24V general 
thermostat.

 

 

Содержание TTWA Series

Страница 1: ...ded by YMGI Failure to follow and adhere to all codes and documentation can cause damage to equipment property even personal injury Installer Currently licensed certified HVAC technicians only Must Re...

Страница 2: ...s and LCDI Cords 17 Installation Instructions 18 Wall Sleeve Assembly 19 Outdoor Grille Installation 20 Vent Control and Air Direction 22 Maintenance and Cleaning 24 Wiring 25 Unit Features 26 Operati...

Страница 3: ...the wall installation in new or existing buildings To complete the installation of this TTWA an insulated wall sleeve and an outdoor grille either the stamped aluminum grille or the architectural gril...

Страница 4: ...ing and recycling of certain refrigerants the equipment and tools necessary to perform these service procedures In addition some states or municipalities may have additional requirements that must als...

Страница 5: ...soon as possible and provide the following information Data on the unit model number serial number and owner s name A detailed description of the unit s problem before and after the problem occurred...

Страница 6: ...equire certified and licensed personnel to install Reading and following YMGI Group recommendations and requirements contained in the following pages and other documents is the first step to help ensu...

Страница 7: ...through any structures at time of installation 2 Not installing an oil P trap in the copper suction line where the indoor unit is located 18 feet or more below the outdoor unit 3 Cross piping and or...

Страница 8: ...date from YMGI Group whichever comes first This is a standard limited liability warranty and DOES NOT cover the following Any damage or repairs to properties or persons as an incident of or consequen...

Страница 9: ...ill ground ship out the parts ASAP Expedited shipping is available at the customer s expense 4 Replacement parts that have an approved warranty registration are to be warranted for the remainder of th...

Страница 10: ...YMGI Your Modern Green Idea 10...

Страница 11: ...not set the indoor unit s room temperature too low Keeping the temperature difference between indoor and outdoor unit within 41 5 18 YMGI Group recommends that only properly trained and authorized pe...

Страница 12: ...ected and the circuits are switched on could cause an electrical shock or fire DO NOT install the indoor unit near any cooking surfaces in direct sunlight or any ventilation systems Poor placement cou...

Страница 13: ...8 3 9 9 7 4 9 3 9 4 9 Locked rotor Amp LRA A 23 8 41 5 21 54 28 5 21 28 5 Capacitor uF 35 60 30 60 40 30 40 Indoor fan motor Model YDK 30B 6P2 YDK 30B 6P2 YDK 30B 6P2 YDK 30B 6P2 YDK 30B 6P2 YDK 30B 6...

Страница 14: ...ts 34 U 36 U 36 U 34 U 34 U 36 U 34 U Outdoor sound level sound pressure level Cooling dB A 67 64 67 64 67 64 67 64 67 64 67 64 67 64 Unit Dimension W D H In 26 x 21 57 x 15 59 26 x 21 57 x 15 59 26 x...

Страница 15: ...t RLA A 7 8 2 9 3 9 4 9 Locked rotor Amp LRA A 41 5 15 21 28 5 Capacitor uF 60 20 30 40 Indoor fan motor Model YDK 30B 6P2 YDK 30B 6P2 YDK 30B 6P2 YDK 30B 6P2 Input W 64 64 64 64 Output W 30 30 30 30...

Страница 16: ...sound pressure level Cooling dB A 67 64 67 64 67 64 67 64 Unit Dimension W D H In 26 x 21 57 x 15 59 26 x 21 57 x 15 59 26 x 21 57 x 15 59 26 x 21 57 x 15 59 Packing W D H In 30 12 x 24 8 x 18 9 30 12...

Страница 17: ...n of this product Refer to the data specification plate for electrical requirements LCDI Cords Underwriters Laboratories and the National Electric Code NEC now require power cords that can sense curre...

Страница 18: ...Code The proper installation of this unit is described in the following sections Following the steps in the order presented should ensure proper installation HIGH VOLTAGE DISCONNECT ALL POWER BEFORE S...

Страница 19: ...ion In order for condensate water to drain properly inside the unit the sleeve must be installed properly Level from right to left A slight downward pitch from the indoor side to the outdoor side as s...

Страница 20: ...ineer and confirm that the new chassis can be used with the non standard specialized grille An improper outdoor grille may cause poor cooling or heating effect a higher power input and shorten the uni...

Страница 21: ...sis part of the way into the sleeve and reattach the ground wire back to the hole on the right side on the control panel area next to the ground symbol 3 Remove shipping pads inside air conditioner ne...

Страница 22: ...ocated behind the front grille on the right side of the air discharge area When set at CLOSE only the air inside the room will be circulated and conditioned When set at OPEN some inside air is exhaust...

Страница 23: ...NOTES 1 The unit is equipped with a rubber grommet mounted compressor These grommets are set at the factory and do not need to be adjusted 2 Check if there are any obstruction before the indoor and ou...

Страница 24: ...ecessary to remove the front panel 2 Filter is removed by opening the grille panel and gently pulling forward Vent Screen Before cleaning the vent screen disconnect power to the unit by unplugging the...

Страница 25: ...FIRST OPENING ALL DISCONNECTS AND OR REMOVING THE UNIT CORD SET PLUG FROM THE WALL OUTLET TO AVOID THE RISK OF ELECTRIC SHOCK PERSONAL INJURY OR PROPERTY DAMAGE DO NOT USE AN EXTENSION CORD WITH THIS...

Страница 26: ...sensors to maximize comfort conditions for the room occupant and provide outstanding features Thermistors are used to sense small changes in temperature and allow the microprocessor to monitor and re...

Страница 27: ...YMGI Your Modern Green Idea 27 OPERATING INSTRUCTIONS...

Страница 28: ...troduction of LCD screen icons Mode display Temperature display Timer display Range can be set between 16 32 C or 61 90 F TIMER ON is set Cooling mode TIMER OFF is set Fan mode Other display icons Hea...

Страница 29: ...GY SAVER button the green LED indicator turns off 1 Reset Filter means the indoor fan has been running for 250 hours accumulated It is time to clean the filter After finishing cleaning press this butt...

Страница 30: ...ller it could be used for the air conditioners with multifunction For some functions that the model doesn t have if press the corresponding button on the remote controller the unit will keep the origi...

Страница 31: ...through the power press ON OFF button on the remote controller to turn on the air conditioner 2 Press MODE button to select your required mode 3 Press or button to set your required temperature 4 Pres...

Страница 32: ...reaches 13 C 55 F will heating stop 6 Electric Power Off Memory When the power is turned on the unit will operate using the same settings as before power off The default setting is enabled UP 7 Clean...

Страница 33: ...ets the operational mode of the fan In ON position the fan will run continuously whenever power is applied in this mode In AUTO position the fan will cycle on and off with the compressor or electric h...

Страница 34: ...the unit that block the room return air flow if so remove the obstacle 2 Check the indoor fan make sure it is running properly if not repair the fan 3 Check the related sensor plug make sure that it...

Страница 35: ...t restricting or blocking unit airflow Reset to a lower or higher temperature setting Remove and clean filters Allow sufficient amount of time for unit to heat or cool the room Start heating or coolin...

Страница 36: ...7 524 1 00 4 00 122 0 2 096 2 138 2 180 3 34 1 66 23 0 16 090 16 431 16 733 1 04 3 96 123 8 2 030 2 071 2 112 3 37 1 63 24 8 15 418 15 739 16 060 1 07 3 93 125 6 1 966 2 006 2 047 3 41 1 59 26 6 14 77...

Страница 37: ...YMGI Your Modern Green Idea 37 TTWA Wiring Diagrams TTWA0 Wiring Diagram AC Only...

Страница 38: ...YMGI Your Modern Green Idea 38 TTWA0 Wiring Diagram AC Heater...

Страница 39: ...YMGI Your Modern Green Idea 39 TTWA0 Wiring Diagram HP...

Страница 40: ...YMGI Your Modern Green Idea 40 TTWA0 Wiring Diagram HP Heater...

Страница 41: ...1 USER NOTES AND INSTALLATION SERVICE MAINTENANCE NOTES INSTALLATION NOTES Put down any questions comments or problems you have experienced as a unit history No Date Notes Asked Technician for Help Di...

Страница 42: ...dea 42 USER NOTES Put down whatever questions you have or problems you have seen as a unit history No Date Company Name Technician Name Phone HVAC License Job Not Performed by Technician Technician Ch...

Страница 43: ...YMGI Your Modern Green Idea 43 SERVICE MAINTENANCE NOTES No Date Service Maintenance Company Name Technician Name Phone HVAC License...

Страница 44: ...tu h 58 4 78 1 Single Zone 18 23 SEER 09 36K Btu h Symphony CHOIR DC Inverter 59 2 DC Inverter Multiple Zone 16 SEER 2x09K to 5x12K Btu h 59 2S DC Inverter Multiple Zone 16 SEER 6x09K to 9x09K Btu h 5...

Отзывы: