13

 

 

Maintenance

Compressor Oil 

 

The oil should be checked for contamination and 
proper oil level when the compressor oil mainte-
nance reminder is displayed. Select RESET to turn 
reminder off until the next time you start the unit. 
Select ENTER to reset the reminder until the next 
scheduled maintenance.  

 

Instructions for Oil Maintenance 

 

Oil Level Check 
1.  Place unit on a level surface and run a recovery  

cycle with the unit. 

2.  Unplug unit. 
3.  Remove front cover of unit. 
4.  SLOWLY remove oil port cap on compressor. 

 

Note: High pressure may be present, remove cap 
slowly. 

 

5.  Place rear wheels of unit on a 2 x 4. 
6.  Oil should drip out of oil drain port. 
7.  If oil runs out of port rapidly, allow to drain. 
8.  Replace oil port cap and cover. 
9.  Dispose of oil properly. 

Oil Replacement Procedure 

 

1.  Follow steps 1 thru 4 in the oil level check. 
2. 

Tilt unit at 45° angle towards oil drain. port until 

all oil has been drained. 

3.  Refill with proper amount and type of oil. The 

proper oil charge is 8.0 ounces 150 VISCOSITY
(SUS) POE oil. 

4.  Replace oil port cap and front cover. 
5.  Dispose of oil properly. 

 

Note: Failure to perform oil maintenance can cause 
the compressor to overfill with oil and severely 
damage the compressor. 
 

Oil 

Drain 

Port 

Maintenance

 Vacuum Pump Oil 

 

Select ENTER to turn the reminder off until the next 
time you start the unit. Select RESET to reset the 
reminder until the next scheduled maintenance.  

 

Check oil level when pump is running.  
When pump is running, oil level should be 1/2 to 5/8 
up in the sight glass. This level is necessary for 
proper operation. 

 

This maintenance is best performed when the oil    
is warm. 

1.  Remove thumb screws under vacuum pump. 
2.  Rotate the front of the vacuum pump towards 

the rear of the unit. 

3.  Place a container under the oil drain plug and      

remove the oil drain plug. 

4.  Drain oil into the container. 
5.  Dispose of the oil properly. 
6.  Refill the vacuum pump with YELLOW JACKET 

(Quart Part no. 93192) vacuum pump oil to the   
correct level. 

7.  Reverse Steps 1-2. 

Calibration Check (1 lb weight) 
1.  Select SETUP in the main menu 
2.  Select CALIBRATION CHECK 
3. 

Press “START” key to stabilize

 

4. 

After stabilizing, machine will display “PLACE 
THE 1lb TEST WEIGHT ON THE TANK” (1lb 

weight supplied) 

5. 

Press the “START” key

 

Example: 

1 lb. 02 oz (Out of Calibration)   

                  

0 lb. 15.98 oz (Out of Calibration) 

 
NOTE: If out of calibration follow the steps dis-
played on the display to recalibrate scale 
 
 

“WARNING SCALE CALIBRATION” MESSAGE

If the scale calibration changes, this message may    
appear on the display. To reset the warning mes-
sage follow the on screen instructions or do the 
following: 
1.  Select SETUP in the main menu 
2.  Select CALIBRATE SCALE 
3. 

The display will then read “REMOVE WEIGHT 
FROM SCALE”

 

4.  Once the weight is removed press the  START 

key 

5. 

The display will then read “CALIBRATING 
PLEASE WAIT”

 

6. 

When the display reads “POWER OFF AND RE-
START SYSTEM” turn the main power switch off

 

7.  Carefully place the tank back on the scale and 

turn the main power switch back on. 

Содержание 3788 Series

Страница 1: ...Operation Manual 37837 37880 37881 37882 37887 37888 37889 3788X Series includes 37837 P N 380539 RevF...

Страница 2: ...Deliberate inhalation of refrigerants is ex tremely dangerous Death can occur without warning Vapors reduce oxygen available for breathing and are heavier than air De composition products are hazardo...

Страница 3: ...por form is a potentially hazardous material Please consult the manufacturer s Material Safety Data Sheet for additional information and adhere to the following safety guidelines Avoid breathing high...

Страница 4: ...Low Gauge 4 Auto High Side Hose Red 5 Auto Low Side Hose Blue 6 Tank Vapor Hose Red 7 Tank Liquid Hose Blue 8 Oil Drain Bottle 9 Oil Inject Bottle excluded on 37837 37887 and 37888 10 Tool Tray 11 Ma...

Страница 5: ...Option 2 Vacuum is used to vacuum air moisture from a system previously opened to the atmosphere This Option will then proceed to recharge the A C system This Option also allows the technician to veri...

Страница 6: ...system problem Ensure the automobile A C system is turned off prior to selecting a mode on the machine 3 Connect the high and low side auto service hoses to the respective high and low side ser vice...

Страница 7: ...NTIES AND MY CAUSE DAMAGE TO OTH ER AUTOMOBILES THAT YOU SERVICE IN THE FU TURE RECOVER cont VACUUM The vacuum function of the 37880 SERIES is de signed to remove air moisture from the automobile A C...

Страница 8: ...X 1 Verify the auto air conditioning system is off 2 Select CHARGE option from the main menu 3 When the LCD reads SET CHARGE AMOUNT set the amount of refrigerant to be charged into the A C system by u...

Страница 9: ...he hold time will count down on the LCD and the unit will beep at the end of the hold time If vacuum hold time was set to zero the unit will transition into charge mode 11 Record the final vacuum leve...

Страница 10: ...a hybrid A C system can cause serious issues with the electrical system Having too much of the wrong type of oil in a hybrid A C system can conduct the electricity to the outside of the A C compressor...

Страница 11: ...follow the instructions on the screen and the unit will clear itself automatically Repeat the identification process to insure the proper identification of the refrigerant purity level If the unit fa...

Страница 12: ...nged periodically to ensure the system is working properly A maintenance reminder prompts you when to change your filters All refrigerant must be removed from the old filters before they are removed F...

Страница 13: ...d maintenance Check oil level when pump is running When pump is running oil level should be 1 2 to 5 8 up in the sight glass This level is necessary for proper operation This maintenance is best perfo...

Страница 14: ...o a 120 Volt outlet Circuit breaker tripped on shop power panel Bad Main Power switch Loose wire Bad Transformer on microprocessor board Plug into outlet Reset circuit breaker If circuit breaker immed...

Страница 15: ...SCALE CALIBRATION ERROR 6 TANK EMPTY REFRIGERANT BELOW 5 OF TANK CAPACITY REFILL TANK CHECK SCALE CALIBRATION ERROR 7 NOT ENOUGH REFRIGERANT UNIT IS LOW ON REFRIGERANT 10 LB MIN REFILL TANK ERROR 8 TA...

Страница 16: ...ges Series 41 Manifold valves can be reconditioned using replacement seating cylinder 41133 There will be a reconditioning charge for manifolds returned to the factory for repair If found defective we...

Отзывы: