Figure 4 

– CONTROL BOX LAYOUT 

 

 

 

 

Fuse Rating Chart 

Symbol 

Amps  Replacement 

F2 

Bussmann Model 
GLQ-3, GMQ-3 or 
GMQ-3-2/10, Rated 
300vac. 

F4 

Fuji Model FGAO-2, 
Rated 250vac. 

F11, F12 

Fuji Model FGAO-2, 
Rated 250vac. 

F31, F32 

Fuji Model FGAO-2, 
Rated 250vac. 

FB11, 

FB12 

Fuji Model FGAO-2, 
Rated 250vac. 

FB21, 

FB22 

15 

Nagasawa Model 
GAB 

FP 

Fuji Model FGAO-2, 
Rated 250vac. 

FT1, FT2, 

FT3 

Fuji Model FGAO-2, 
Rated 250vac. 

Figure 5 

– FUSE PANEL 

Содержание CH-K100

Страница 1: ...UCTIONS and properly maintained it can provide many years of trouble free operation CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 2 HEATING OPERATION 3 CONTROLS GENERAL INFORMATION 4...

Страница 2: ...cooled and heat is normally rejected to a cooling tower though ground loop is also an option COOLING OPERATION High Temperature Generator HGE The gas burner heats a dilute lithium bromide solution in...

Страница 3: ...nd semi concentrated solution flow into the primary separator in exactly the same manner as in the cooling cycle Low Temperature Generator LGE In Heat mode the changeover valve opens a path for the se...

Страница 4: ...y also be supervised and controlled by external control systems to a limited degree when the necessary interconnections are installed Additional controls and interlocks can be explained by your ASP On...

Страница 5: ...2 10 Rated 300vac F4 2 Fuji Model FGAO 2 Rated 250vac F11 F12 2 Fuji Model FGAO 2 Rated 250vac F31 F32 1 Fuji Model FGAO 2 Rated 250vac FB11 FB12 2 Fuji Model FGAO 2 Rated 250vac FB21 FB22 15 Nagasaw...

Страница 6: ...on the I O Board to ON The leaving chilled water temperature can be adjusted using the TC potentiometer on the CPU Board The leaving chilled water set point can be set in a range of 40 1 F 4 5 C to 59...

Страница 7: ...ress the alarm RESET button to restart the cooling or heating operation If Error Code 52 is amongst the codes being displayed it will also be necessary to press the RESET button on the burner controll...

Страница 8: ...Gas Pressure Check Supply and Manifold Inhibitor Check If required For the K Series an inhibitor charge is needed every 3 years on average Palladium Cell Heater Check Flow Rate Check Solution Pump Rot...

Страница 9: ...s vacuum section Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate A digital vacuum gauge MUST be used in order to determine the...

Страница 10: ...iller heater itself as well If doing so pressurize the unit to the same pressure as the circuits using nitrogen See the Service Manual for further details TROUBLESHOOTING SYMPTOM Chiller heater does n...

Страница 11: ...iption Notes Reset Type FS Flow switch alarm Chilled hot water flow switch FS1 open but for less than 10 minutes After 10 minutes this changes automatically to error code 27 Auto 01 DCP power error Op...

Страница 12: ...10 C or above 212 F 100 C Ignored for first 10 minutes of P2 operation Manual 36 CND sensor error CND sensor reads below 14 F 10 C or above 212 F 100 C Auto 40 Loss of cooling capacity LT temperature...

Страница 13: ...13 Please send a copy of any maintenance data sheets to Yazaki Energy Systems Inc at the address FAX number and or email address listed on the last page of this document...

Страница 14: ...Labor Charges for warranty service can be obtained by an authorized service provider upon written request to YESI 7 LIMITATION OF WARRANTY AND LIMITATION OF REMEDY CUSTOMER s remedies shall be limite...

Страница 15: ......

Страница 16: ...MS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web http www yazakienergy com This symbol on the product s name plate means i...

Отзывы: