Setting
Function
Page
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
1B
During Baseblock (N.C.)
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
2F
Maintenance Period
37
During Frequency Output
38
Drive Enabled
39
Watt Hour Pulse Output
3A
Drive Overheat Alarm (oH2)
3D
During Speed Search
3E
PID Feedback Low
3F
PID Feedback High
4A
During KEB Operation
Setting
Function
Page
4B
During Short Circuit Braking
4C
During Fast Stop
4D
oH Pre-Alarm Time Limit
50
Waiting for Run
51
Sequence Timer 1 Active
52
Sequence Timer 2 Active
53
Sequence Timer 3 Active
54
Sequence Timer 41 Active
58
Underload Detection
60
Internal Cooling Fan Alarm
71
Secondary PI Feedback Low
72
Secondary PI Feedback High
A4
BP Drive Relay
A5
BP Bypass Relay
A6
BP BAS Interlock Relay
A9
Relay Operator Control
B2
BAS Interlock Relay Contact
100 to 1B2 Functions 0 to b2 with Inverse Output
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Description
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ON
OFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 1.39 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.
Status
Description
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
OFF
Output frequency
Zero Speed
ON
E1-09 (Min. Output Frequency) or
b2-01 (Zero Speed Level)
Figure 1.40 Zero-Speed Time Chart
1.7 H: Terminal Functions
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
83
1
Parameter Details