Frequency reference
+
L4-04
Frequency reference – L4-04
L4-03
L4-03
+
L4-04
L4-03 – L4-04
Frequency reference
0 Hz
OFF
OFF
ON
ON
Frequency reference
During
Forward
Output frequency
Output frequency
User Set
Speed Agree 2
Figure 1.46 User-Set Speed Agree 2 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 110
Setting 15: Frequency Detection 3
The output opens when the output frequency or motor speed rises above the detection level set in L4-03 plus the detection
with set in L4-04. The terminal remains open until the output frequency or motor speed falls below the level set in L4-03. The
detection level L4-03 is a signed value; detection works in the specified direction only.
Status
Description
Open
Output frequency or motor speed exceeded L4-03 plus L4-04.
Closed
Output frequency or motor speed is below L4-03 or has not exceeded L4-03 plus L4-04.
L4-04
Frequency
detection 3
ON
OFF
L4-03
Output Frequency
Figure 1.47 Frequency Detection 3 Example with a Positive L3-04 Value
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 110
Setting 16: Frequency Detection 4
The output closes when the output frequency or motor speed is above the detection level set in L4-03. The terminal remains
closed until the output frequency or motor speed falls below L4-03 minus the setting of L4-04.
Status
Description
Open
Output frequency or motor speed is below L4-03 minus L4-04 or has not exceeded L4-03.
Closed
Output frequency or motor speed exceeded L4-03.
Note:
The detection level L4-03 is a signed value; detection works in the specified direction only.
1.7 H: Terminal Functions
88
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual