73
• Overtorque detection function selection (n59)
(1) To detect overtorque at accel/decel, set to 3 or 4.
(2) To continue the operation after overtorque detection, set to 1 or 3.
During detection, the operator displays “
” alarm (blinking).
(3) To halt inverter by a fault at overtorque detection, set to 2 or 4. At detection, the
operator displays “
” fault (ON).
• Overtorque detection level (n60)
Sets the overtorque detection current level in units of 1%. (Inverter rated current =
100%)
Factory setting: 160%
• Overtorque detection time (n61)
If the time when the motor current exceeds the overtorque detection level (n61),
the overtorque detection function operates.
Factory setting: 0.1sec.
Setting
Description
0
Overtorque detection not provided
1
Detected during speed agree, (alarm).
Operation continues after detection.
2
Detected during speed agree (fault). Operation stops during
detection.
3
Detected during running,
operation continues after detection. (alarm).
4
Detected during running,
operation stops during detection. (fault).
All manuals and user guides at all-guides.com
Содержание VS MINI J7 series
Страница 13: ...13 2 IDENTIFYING THE PARTS All manuals and user guides at all guides com...
Страница 14: ...14 Notes All manuals and user guides at all guides com...
Страница 21: ...21 Standard Wiring All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 23: ...23 Dimensions All manuals and user guides at all guides com...
Страница 34: ...34 Notes All manuals and user guides at all guides com...
Страница 38: ...38 Notes All manuals and user guides at all guides com...
Страница 56: ...56 Notes All manuals and user guides at all guides com a l l g u i d e s c o m...
Страница 98: ...98 Notes All manuals and user guides at all guides com...
Страница 102: ...102 NOTES All manuals and user guides at all guides com...