3.3 Wiring Main Circuit Terminals
3
-9
2. If ambient temperature exceeds 30
°
C (86
°
F
), the allowable current of wire may be lowered.
3. Temperature for each wire indicates the maximum allowable conductor temperature.
Table 3.3
200 V Class Inverter Power Cable Specifications
Wire Sizes
Model CIMR-
M5
Terminal Symbols
Terminal
Screw
Tighten-
ing
Torque
(N
S
m)
UL-approved
75
°
C (167
°
F)
Temperature-rated
Copper Wire
[AWG (mm
2
)]
600 V Vinyl-
sheath Insulated
Wire (IV, VV)
60
°
C (140
°
F)
(mm
2
)
600 V Cross-
linked Polyethy-
lene Wire (IC)
90
°
C (194
°
F)
(mm
2
)
600 V Rubber-in-
sulated Cabtyre
Cable (CT)
60
°
C (140
°
F)
(mm
2
)
P/
¨
, N/
©
M6
2.94
(*1)
23P7
U/T1, V/T2, W/T3
M5
2.35
8 (8.4)
5.5
3.5
5.5
M5
×
2
2.35
10 (5.3)
3.5
2
3.5
P/
¨
, N/
©
M6
2.94
(*1)
25P5
U/T1, V/T2, W/T3
M5
2.35
8 (8.4)
5.5
3.5
5.5
M5
×
2
2.35
10 (5.3)
3.5
2
3.5
P/
¨
, N/
©
M6
2.94
(*1)
27P5
U/T1, V/T2, W/T3
M5
2.35
8 (8.4)
8
3.5
8
M5
×
2
2.35
8 (8.4)
5.5
3.5
5.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
2011
U/T1, V/T2, W/T3
M8
6.47
6 (13.3)
14
8
14
M6
×
2
3.4 to 4.9
8 (8.4)
8
5.5
5.5
P/
¨
, N/
©
M6
×
2
2.94
(*1)
2015
U/T1, V/T2, W/T3
M8
6.47
4 (21.2)
22
14
22
M6
×
2
3.4 to 4.9
6 (13.3)
14
8
8
P/
¨
, N/
©
M6
×
2
2.94
(*1)
2018
U/T1, V/T2, W/T3
M8
6.47
3 (26.7)
30
14
30
M6
×
2
3.4 to 4.9
6 (13.3)
14
8
14
P/
¨
, N/
©
M6
×
2
2.94
(*1)
2022
U/T1, V/T2, W/T3
M8
6.47
2 (33.6)
50
22
38
M6
×
2
3.4 to 4.9
6 (13.3)
14
8
14
P/
¨
, N/
©
M6
×
2
2.94
(*1)
2030
U/T1, V/T2, W/T3
M8
7.8 to 9.8
2/0 (67.4)
80
38
80
M6
×
2
3.4 to 4.9
4 (21.2)
22
14
14
P/
¨
, N/
©
M6
×
4
2.94
(*1)
2037
U/T1, V/T2, W/T3
M10
14.7 to
19.6
3/0 (85.0)
100
50
100
2037
M8
×
2,
7.8 to 9.8
3 (26 7)
22
14
22
M8
×
2,
M6
3.4 to 4.9
3 (26.7)
22
14
22
2011 to
2037
A12/r2, A22/t2 (*2)
M4
1.2 to 2.0
14 (2.1)
2
2
2
* 1. Connect using exclusive-use connection bus bar.
* 2. Provided for open chassis type with a minimum capacity of 11 kW. Not provided for external heatsink cooling type.
Notes: 1. Wire size is selected assuming external suspended wiring of single 3-core cables at
an ambient temperature of 30
°
C (86
°
F
).
2. If ambient temperature exceeds 30
°
C (86
°
F
), the allowable current of wire may be lowered.
3. Temperature for each wire indicates the maximum allowable conductor temperature.
3