n
Transfer via MPI
n
Transfer via Ethernet
n
Transfer via memory card
5.9.1 Transfer via MPI
For transfer via MPI there is the following interface:
n
X2: MPI interface
The structure of a MPI net is electrically identical with the structure of a PROFIBUS net.
This means the same rules are valid and you use the same components for the build-up.
The single participants are connected with each other via bus interface plugs and
PROFIBUS cables. Per default the MPI net runs with 187.5kbaud. VIPA CPUs are deliv-
ered with MPI address 2.
The MPI programming cables are available at VIPA in different variants. The cables pro-
vide a RS232 res. USB plug for the PC and a bus enabled RS485 plug for the CPU. Due
to the RS485 connection you may plug the MPI programming cables directly to an
already plugged plug on the RS485 jack. Every bus participant identifies itself at the bus
with an unique address, in the course of the address 0 is reserved for programming
devices.
A cable has to be terminated with its surge impedance. For this you switch on the termi-
nating resistor at the first and the last participant of a network or a segment. Please make
sure that the participants with the activated terminating resistors are always power sup-
plied. Otherwise it may cause interferences on the bus.
1
MPI programming cable
2
Activate the terminating resistor via switch
3
MPI network
1.
Connect your PC to the MPI jack of your CPU via a MPI programming cable.
2.
Load your project in the Siemens SIMATIC Manager.
3.
Choose in the menu
‘Options
è
Set PG/PC interface’
.
4.
Select in the according list the "PC Adapter (MPI)"; if appropriate you have to add it
first, then click on [Properties].
5.
Set in the register MPI the transfer parameters of your MPI net and type a valid
address
.
6.
Switch to the register
Local connection
.
General
Net structure
MPI programming cable
Terminating resistor
Proceeding transfer via
MPI interface
VIPA System 300S
+
Deployment CPU 312-5BE23
Project transfer > Transfer via MPI
HB140 | CPU-SC | 312-5BE23 | en | 18-45