4
Precautions for CE Markings
•
Only basic insulation to meet the requirements of protection class I and over voltage category II is
provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to CE requirements.
•
For 400 V class Inverters, make sure to ground the supply neutral
to conform to CE requirements.
•
For conformance to EMC directives, refer to section 3 in this document. For details, refer to the
following document: Document No. EZZ008390 for English version
Receiving
Mounting
CAUTION
Use 75 C copper wires or equivalent.
Low voltage wires shall be wired with Class I Wiring.
CAUTION
•
Do not install or operate any Inverter That is damaged or has missing parts.
Failure to observe this caution may result in injury or equipment damage.
CAUTION
•
Lift the Inverter by the heatsink. When moving the Inverter, never lift it by the
plastic case or the terminal covers.
Otherwise, the main unit may fall and be damaged.
•
Mount the Inverter on nonflammable material (i.e., metal).
Failure to observe this caution may result in a fire.
•
When mounting Inverters in an enclosure, install a fan or other cooling device to
keep the intake air temperature below 122
°
F (45
°
C) for IP20 (open chassis type),
or below 105
°
F(40
°
C) for NEMA1 (TYPE1).
Overheating may cause a fire or damage the Inverter.
•
The VS-V7AZ generates heat. For effective cooling, mount it vertically.
Refer to the figure in Mounting Dimensions on section 3.