2.3
OPERATION ERRORS
After the constants have been set, an operation error will occur if there is an invalid
setting or a contradiction between two constant settings.
It won’t be possible to start the power regenerative unit until the constants have been
set correctly. (The minor fault output and fault contact output will not operate, ei-
ther.)
When an operation error has occurred, refer to the following table to identify and cor-
rect the cause of the errors.
Table A-
5
Operation Error Displays and Incorrect Settings
Display
Meaning
Incorrect settings
OPE01
kVA Selection
Incorrect Power Regenerative
Unit Capacity Setting
The power regenerative unit capacity setting does not match the
Unit. (Contact your YASKAWA representative.)
OPE02
Limit
Constant Setting Range Error
The constant setting is outside of the valid setting range.
OPE03
Terminal
Multi-function Input Selection
Error
The same setting has been selected for two or more multi-function
inputs (H1-01, H1-02)