(2) Input AC Reactor
An input 3-phase reactor corresponding to each model is necessary when operat-
ing VS-656RC5. This input AC reactor is effective against saturated current and
excessive heat.
Table 5 shows the code numbers of AC reactor of each model. Check the table
and use a specified AC reactor.
Table
5
AC Reactor
VS-656RC5
Power coordinating reactor
Power Suppressing Reactor
Model CIMR-R5U
j
Rated
current
(Arms)
Inductance
(mH)
Code No.
Rated
current
(Arms)
Inductance
(mH)
Code No.
23P7
20
0.53
X002491
15
0.31
X010121
25P5
30
0.35
X002492
15
0.31
X010121
27P5
40
0.265
X002493
20
0.15
X010122
200 V
2011
60
0.18
X002495
40
0.1
X010123
200 V
Class
2015
80
0.13
X002497
40
0.1
X010123
Class
2018
90
0.12
X002498
50
0.06
X010124
2022
120
0.09
X002555
60
0.05
X010125
2030
160
0.07
X002556
80
0.04
X010126
2037
200
0.05
X002557
100
0.03
X010127
43P7
10
2.2
X002500
7.5
1.2
X010128
45P5
15
1.42
X002501
7.5
1.2
X010128
47P5
20
1.06
X002502
10
0.6
X010129
4011
30
0.7
X002503
15
0.4
X010130
4015
40
0.53
X002504
25
0.3
X010131
400 V
4018
50
0.42
X002505
25
0.3
X010131
400 V
Class
4022
60
0.36
X002506
30
0.2
X010132
4030
80
0.26
X002508
40
0.15
X010133
4037
90
0.24
X002509
50
0.12
X010134
4045
120
0.18
X002566
60
0.1
X010135
4055
150
0.15
X002567
75
0.08
X010136
4075
200
0.11
X002568
100
0.06
X010137