YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure

U1000 iQpump Drive 

Quick Start Procedure

Page 8 

of 25

 

 Select Start/Stop and Speed Method (continued)

4

STEP

Parameter C1-02 Setting Example

Press                 key to display the main menu.  

3X

U1-02=   0.00Hz

U5-99=     0.0

PSI

 

Auto Setpoint

- MODE -          DRV Rdy

U1-91=   0.0PSI

MONITOR

LSEQ

LREF

Programming

- MODE -          PRG

FWD

HOME

Select language

- PRMSET-        PRG

Select Language

A

1-=          0

FWD

HOME

Select Digit

00

Basic Setup

- PRMSET-        PRG

Select Language

FWD

HOME

C

1-=          0

00

Increase/Decrease Selection

Accel Time 1

- PRMSET-        PRG

(0.0~6000.0)

   '20.0

sec

'

FWD

HOME

C

1- 

01

        20.0

sec

Increase/Decrease Selection

Press twice to

go to the next digit.

Decel Time 1

- PRMSET-        PRG

(0.0~6000.0)

   '10.0

sec

'

FWD

HOME

C

1- 

02

=

         10.0

sec

Decel Time 1

- PRMSET-        PRG

(0.0~6000.0)

   '10.0

sec

'

FWD

HOME

C

1- 

02= 

    00

1

0

.0

sec

to edit mode.

Press                   to switch

Modify Value

new value.

Decel Time 1

- PRMSET-        PRG

(0.0~6000.0)

   '10.0

sec

'

FWD

HOME

C

1- 

02= 

    00

2

0

.0

sec

Press                   to save

F1

Press                 to return to the main menu.

F1

4.6 Example of Setting Parameters

 

 DO NOT RUN THE MOTOR. Ensure all protective covers are installed and power is 

turned on.

Refer to Parameter C1-02 Setting Example

 

below for information on how to access and set parameters.

Содержание U1000 iQpump Drive

Страница 1: ...U1000 iQpump Drive Low Harmonic Regenerative Pump Controller Models 200 V Class 10 to 100 HP ND 400 V Class 7 5 to 350 HP ND Type CIMR UW MANUAL NO TOEPYAIUPW02A PUBLISHED FEBRUARY 2017 Revision 1 DR...

Страница 2: ...POWER 5 STEP 4 SELECT START STOP AND SPEED METHOD 6 STEP 5 REAL TIME CLOCK SETUP 9 STEP 6 APPLICATION SETUP 10 STEP 7 PARAMETER OVERVIEW QUICK SETTING MENU SIMPLEX 12 STEP 8 FINE TUNE SETTINGS FOR PU...

Страница 3: ...t run operation Refer to the U1000 iQpump Drive User Manual No TOEPYAIUPW01 for complete instructions to configure this product for each specific installation site Terminology U1000 iQpump Drive is re...

Страница 4: ...mful gases and liquids excessive vibration chlorides direct sunlight Altitude 1000 m 3281 ft or lower up to 3000 m 9843 ft with derating Vibration 20 to 55 Hz 5 9 m s2 2o0104 to 2o0248 4o0096 to 4o041...

Страница 5: ...d wiring practices and applicable electric codes Ensure all equipment is properly grounded WARNING Fire Hazard Do not connect terminals p1 or n1 terminals to earth ground Only connect ground wiring to...

Страница 6: ...AC A1 A2 A3 FM AM AC 24V RP AC M1 M2 M3 M4 MD ME MF MA MB MC Jumper Run FWD Drive I O Terminals 4 3 Select Start Stop Control Method START STOP from the HOA keypad is the default start stop method If...

Страница 7: ...Figure 4 4 3 Wire 0 to 10 V Transducer Parameter H3 09 Details Shield 24V Power Supply Transducer Signal 0 10 Vdc typical Example Customer supplied pressure transducer feedback device Supply Common 2...

Страница 8: ...ncrease Decrease Selection Accel Time 1 PRMSET PRG 0 0 6000 0 20 0sec FWD HOME C1 01 20 0sec Increase Decrease Selection Press twice to go to the next digit Decel Time 1 PRMSET PRG 0 0 6000 0 10 0sec...

Страница 9: ...Note After the real time clock is set the real time clock setup screen will not display again unless parameter o4 17 is set to 1 5 1 Power up the drive and set the Real time Clock The Real time Clock...

Страница 10: ...l PSI 6009 Pump Down Level Mode Ft 6011 VTC Pressure Control Mode 6012 VTC Pivot Panel Mode 6013 Advanced Pressure Control Mode 6014 Pivot Panel Submersible Mode 7770 General Purpose 7771 General Purp...

Страница 11: ...lue Modify Value ENTER ENTER ENTER U1 02 0 00Hz U5 99 0 0PSI Auto Setpoint MODE DRV Rdy U1 91 0 0PSI MONITOR LSEQ LREF Pump Quick Setup MODE PRG FWD HOME 1 10 16 50 Motor Rated FLA SETUP PRG 7 00A FWD...

Страница 12: ...n the display Pump Quick Setup 2 7 4 System Scaling Enter feedback device maximum Example Enter 200 for pressure transducer with a maximum of 200 PSI at 20 mA Confirm feedback device scaling Refer to...

Страница 13: ...ta value from the setpoint Example Start Draw Down Level P1 04 set to 10 PSI with a system setpoint of 50 PSI and delay time P1 05 set to 5 seconds Result Pump system will start when the pressure drop...

Страница 14: ...le 200 0 PSI WAIT SYSTEM STARTS WHEN PRESSURE SIGNAL FALLS BELOW 100 PSI 50 0 PSI 150 200 PSI P1 03 200 0 Feedback Scaling Example PSI P1 02 1 8 1 System Feedback Unit Feedback Device Scaling 8 2 Star...

Страница 15: ...cess motor wear when using a submersible motor in combination with the drive Enter the minimum motor frequency in parameter P4 11 to enable this function Example Minimum motor speed 1800 RPM 1800 RPM...

Страница 16: ...Display No alarm active Auto Mode Off Hand Mode Off U1 02 0 00Hz U5 99 0 0PSI MODE DRV Rdy U1 91 0 0PSI MONITOR LSEQ LREF Auto Setpoint 9 2 Motor Rotation Test Standard The LED should be ON The motor...

Страница 17: ...of motor rotation 9 4 Feedback Signal Check Verify Feedback on Display Refer to parameter P1 02 and P1 03 if the feedback device scaling or system units are incorrect Verify feedback on display match...

Страница 18: ...y U1 91 56 2PSI MONITOR LSEQ LREF Auto Setpoint 10 2 Set System Setpoint Press to access or modify the system setpoint in parameter Q1 01 within the Quick Setup Menu Press to select the digit and to c...

Страница 19: ...z U5 99 0 0PSI Auto Setpoint MODE DRV Rdy U1 91 56 2PSI MONITOR LSEQ LREF The drive starts in AUTO mode when the feedback signal falls below the programmed level in parameter P1 04 for the time specif...

Страница 20: ...eed Use to change HAND Speed value Adjust Hand Speed from Analog Input 0 10 V 0 10 V Connection 0 10 Vdc V AC A1 A2 A3 FM AM AC RP AC 24V Cable Shield E G Set parameter P5 01 HAND Mode Ref to 0 to adj...

Страница 21: ...of parameter b5 13 2 Fault 12 3 Adjust depending on system performance C1 01 Acceleration Time 1 Sets the time to accelerate the pump motor from zero to maximum speed Programming NOTE The factory def...

Страница 22: ...leep Mode when the selected signal level P2 01 falls below the specified sleep level P2 02 5 seconds 12 8 Primarily used for submersible pumps Program P4 12 0 0 Hz to disable function when the drive i...

Страница 23: ...fy system pressure feedback U1 91 If the pressure drops more than 3 PSI U1 91 adjust P2 25 to the actual delta pressure drop plus 1 PSI Example Setpoint is 80 PSI Pressure feedback U1 91 displays 76 P...

Страница 24: ...YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure NOTES U1000 iQpump Quick Start Procedure Page 24 of 25...

Страница 25: ...YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure U1000 iQpump Quick Start Procedure Page 25 of 25 NOTES...

Страница 26: ...0 Fax 55 11 3585 1187 http www yaskawa com br YASKAWA EUROPE GmbH 185 Hauptstra e Eschborn 65760 Germany Phone 49 6196 569 300 Fax 49 6196 569 398 http www yaskawa eu com YASKAWA ELECTRIC KOREA CORPOR...

Отзывы: