![YASKAWA U1000 iQpump Drive Скачать руководство пользователя страница 16](http://html2.mh-extra.com/html/yaskawa/u1000-iqpump-drive/u1000-iqpump-drive_quick-start-quide_3307995016.webp)
YASKAWA TOEPYAIUPW02A U1000 iQpump Drive Quick Start Procedure
U1000 iQpump Drive
Quick Start Procedure
Page 16
of 25
Verify Pump Rotation and Transducer Feedback
9
STEP
9.1 Check the motor for proper direction and operation.
This test is performed solely from the HOA keypad. Apply power to the drive after making electrical connections and installing covers.
The HOA keypad should display as shown in Figure 9.1. The motor should not be running until Step 9.2 is performed.
Figure 9.1 HOA Keypad Display
No alarm active
Auto Mode Off
Hand Mode Off
U1-02= 0.00Hz
U5-99= 0.0
PSI
- MODE - DRV Rdy
U1-91= 0.0PSI
MONITOR
LSEQ
LREF
Auto Setpoint
9.2 Motor Rotation Test (Standard)
The
LED should be ON.
The motor should now be operating and in the correct direction of pump.
Press
on the HOA keypad. The display should read as in Figure 9.1.
Press to access Hand Speed.. Use to change
Hand Speed value. Press to save value.
U1-02= 40.00Hz
U1-01= 40.00
Hz
Hand Reference 1
- MODE - DRV Rdy
U1-91= 32.2PSI
MONITOR
LSEQ
LREF
HAND
Press
on the HOA keypad. The display should read:
OFF
HAND
Press the key to return to the main menu.
F1
Note:
If the direction of rotation is not correct, de-energize the drive and follow step 9.3.