5.8 L: Protection Functions
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
195
P
a
ra
me
te
r D
eta
ils
5
Setting 1: Enabled
When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by increasing the output
frequency.
■
L3-17: Target DC Bus Voltage for Overvoltage Suppression and Stall Prevention
Sets the target DC bus voltage target level used by the overvoltage suppression function (L3-11 = 1) and Intelligent Stall
Prevention during deceleration (L3-04 = 2).
◆
L4: Speed Detection
These parameters set up the speed agree and speed detection functions which can be assigned to the multi-function
output terminals.
■
L4-01, L4-02: Speed Agreement Detection Level and Detection Width
Parameter L4-01 sets the detection level for the digital output functions “Speed Agree 1”, “User Set Speed Agree 1”,
“Frequency Detection 1”, and “Frequency Detection 2”.
Parameter L4-02 sets the hysteresis level for these functions.
Refer to H2-01 to H2-03: Terminal MA, MB and MC, P1-C1 and P2-C2 Function Selection on page 168
, Settings 2, 3,
4, and 5.
■
L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/–)
Parameter L4-03 sets the detection level for the digital output functions “Speed Agree 2”, “User Set Speed Agree 2”,
“Frequency Detection 3”, and “Frequency Detection 4”.
Parameter L4-04 sets the hysteresis level for these functions.
Refer to H2-01 to H2-03: Terminal MA, MB and MC, P1-C1 and P2-C2 Function Selection on page 168
, Settings 13,
14, 15, and 16.
■
L4-05: Frequency Reference Loss Detection Selection
The drive can detect a loss of an analog frequency reference from input A1 or A2. Reference loss is detected when the
frequency reference value reduces for 90% within 400 ms.
Figure 5.72
Figure 5.72 Loss of Reference Function
No.
<1> Values are for 200 V class drives and must be doubled for 400 V class drives.
<2> This value is initialized when E1-01 is changed.
Name
Setting Range
Default
L3-17
Target DC Bus Voltage for Overvoltage Suppression and Stall
Prevention
150 to 400
370 V
No.
Name
Setting Range
Default
L4-01
Speed Agreement Detection Level
–400.0 to 400.0 Hz
0.0 Hz
L4-02
Speed Agreement Detection Width
0.0 to 20.0 Hz
2.0 Hz
No.
Name
Setting Range
Default
L4-03
Speed Agreement Detection Level (+/–)
–400.0 to 400.0 Hz
0.0 Hz
L4-04
Speed Agreement Detection Width (+/–)
0.0 to 20.0 Hz
2.0 Hz
100%
400ms
Analog
frequency
reference
Loss of
Reference
output
time
80%
10%
ON
OFF
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...