5.5 E: Motor Parameters
148
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
■
V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if set up a custom V/f pattern
as shown in
.
Figure 5.33
Figure 5.33 V/f Pattern
Note: 1.
The following condition must be true when setting up the V/f pattern: E1-09
≤
E1-07
≤
E1-06
≤
E1-11
≤
E1-04
2.
To make the V/f pattern a straight line set E1-09 = E1-07. In this case the E1-08 setting is disregarded.
◆
E2: Motor 1 Parameters
These parameters contain the most important motor data needed for optimal motor control. They are set automatically
when Auto-Tuning is performed. If Auto-Tuning can not be performed, then these parameters can be set manually.
■
E2-01: Motor Rated Current
Set E2-01 to the full load amps (FLA) stamped on the motor nameplate. During Auto-Tuning the value must be entered
to parameter T1-04. If Auto-Tuning completes successfully, the value entered will automatically be saved to E2-01.
Note: 1.
Setting units vary by the maximum allowable motor capacity, which is determined by C6-01 and o2-04. Drives up to 11 kW display a
two-digit value, while drives 11 kW and larger display a single-digit value.
2.
Change E2-01 only after changing the value set to E2-03. If E2-01< E2-03, then parameter setting error oPE02 will occur.
No.
<1> Default setting depends on the control mode selection in parameter A1-02. The value shown here is for V/f Control.
Dependent Parameter Default Values on page 364
.
<2> When using OLV/PM control mode, the default setting is determined by the motor code set to E5-01.
<3> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
<4> When E1-13 = 0.0 V, the drive uses the value set in E1-05 to control the voltage.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz
50.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
200.0 V
E1-06
Base Frequency
0.0 to 400.0 Hz
E1-07
Middle Output Frequency
0.0 to 400.0 Hz
2.5 Hz
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V
16.0 V
E1-09
Minimum Output Frequency
0.0 to 400.0 Hz
1.3 Hz
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V
12.0 V
E1-11
Middle Output Frequency 2
0.0 to 400.0 Hz
0.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 to 255.0 V
0.0 V
E1-13
Base Voltage
0.0 to 255.0 V
0.0 V
No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
10% to 200% of the drive
rated current.
(unit: 0.01 A)
Determined by
C6-01 and o2-04
Output Voltage (V)
Frequency (Hz)
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...