5.3 C: Tuning
136
YASKAWA ELECTRIC
SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual
◆
C3: Slip Compensation
The Slip Compensation function prevents motor speed loss due to an increase in load.
Note:
Before making changes to the Slip Compensation parameters, make sure the motor parameters and V/f pattern are set properly or
perform Auto-Tuning.
■
C3-01: Slip Compensation Gain
This parameter sets the gain for the motor slip compensation function. Although this parameter rarely needs to be
changed, adjustments might be needed under the following situations:
• If the speed at constant frequency reference is lower than the frequency reference, increase C3-01.
• If the speed at constant frequency reference is higher than the frequency reference, decrease C3-01.
Note:
This parameter is disabled when using V/f Control with Simple PG Feedback (H6-01 = 3).
■
C3-02: Slip Compensation Primary Delay Time
Adjusts the filter on the output of the slip compensation function. Although this parameter rarely needs to be changed,
adjustments might be needed under the following situations:
• Decrease the setting when the slip compensation response is too slow.
• Increase this setting when the speed is not stable.
Note:
This function is not available when using V/f Control with Simple PG Feedback.
■
C3-03: Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E2-02).
The slip compensation limit is constant throughout the constant torque range. In the constant power range it is increased
based on C3-03 and the output frequency as shown in the following diagram.
Note:
This parameter is disabled when using V/f Control with Simple PG Feedback Control (H6-01 = 3).
Figure 5.25
Figure 5.25 Slip Compensation Limit
■
C3-04: Slip Compensation Selection during Regeneration
When the slip compensation during regeneration function has been activated and regenerative load is applied, it might be
necessary to use a braking option (braking resistor, braking resistor unit, or braking unit).
Even if enabled, this function does not operate when the output frequency is too low.
No.
<1> Default setting depends on the control mode selection in parameter A1-02. The value shown here is for V/f Control.
Dependent Parameter Default Values on page 364
.
Parameter Name
Setting Range
Default
C3-01
Slip Compensation Gain
0.0 to 2.5
0.0
No.
<1> Default setting depends on the control mode selection in parameter A1-02. The value shown here is for V/f Control.
Dependent Parameter Default Values on page 364
.
Parameter Name
Setting Range
Default
C3-02
Slip Compensation Primary Delay Time
0 to 10000 ms
2000 ms
No.
Parameter Name
Setting Range
Default
C3-03
Slip Compensation Limit
0 to 250%
200%
E1-04
E1-06 × C3-03
C3-03
E1-04
Maximum
Frequency
E1-06
Base
Frequency
output frequency
Содержание T1000V
Страница 10: ...10 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 30: ...1 4 Component Names 30 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 44: ...2 2 Mechanical Installation 44 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 100: ...4 10 Test Run Checklist 100 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 232: ...5 12 U Monitor Parameters 232 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 280: ...6 9 Troubleshooting without Fault Display 280 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 294: ...7 5 Drive Replacement 294 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 306: ...8 5 Communication Options 306 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 316: ...A 6 Drive Derating Data 316 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...
Страница 422: ...D 4 Safe Disable Input Precautions 422 YASKAWA ELECTRIC SIEP C710606 44B YASKAWA AC Drive T1000V Technical Manual...