7 Troubleshooting
EN 44
YASKAWA Europe
TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
Ground Fault
• Ground leakage current has exceeded 50%
of the drives rated output current.
• Cable or motor insulation is broken.
• Excessive stray capacitance at drive out-
put.
• Check the output wiring and the motor for
short circuits or broken insulation. Replace
any broken parts.
• Reduce the carrier frequency.
Safe Disable
Both Safe Disable inputs are open. The drive
output is safely disabled and the motor can
not be started.
• Check why the upper controller’s safety
device disabled the drive. Remove the
cause and restart.
• Check the wiring.
• If the Safe Disable function is not utilized
for EN60204-1, stop cat. 0 or for disabling
the drive, the terminals HC, H1, H2 must
be linked.
Safe Disable
Fault
Drive output is disabled while only one of
the Safe Disable inputs is open. (normally
both input signals H1 and H2 should be
open)
• One channel is internally broken and does
not switch off, even if the external signal is
removed.
• Only one channel is switched off by the
upper controller.
• Check the wiring from the upper controller
and make sure that both signals are set cor-
rectly by the controller.
• If the signals are set correctly and the
alarm does not disappear, replace the drive.
Output Phase
Loss
Output cable is disconnected or the motor
winding is damaged.
Loose wires at the drive output.
Motor is too small (less than 5% of drive
current).
• Check the motor wiring.
• Make sure all terminal screws in the drive
and motor are properly tightened.
• Check the motor and drive capacity.
Overcurrent
Short circuit or ground fault on the drive out-
put side
The load is too heavy.
The accel./decel. times are too short.
A magnetic contactor was switched at the
output.
• Check the output wiring and the motor for
short circuits or broken insulation. Replace
the broken parts.
• Check the machine for damages (gears,
etc.) and repair any broken parts.
• Check the drive parameter settings.
• Check the output contactor sequence.
Heatsink
Overheat
Surrounding temperature is too high.
The cooling fan has stopped.
The heatsink is dirty.
The airflow to the heatsink is restricted.
• Check the surrounding temperature and
install cooling devices if necessary.
• Check the drive cooling fan.
• Clean the heatsink.
• Check the airflow around the heatsink.
Motor
Overload
The motor load is too heavy.
The motor is operated at low speed with
heavy load.
Cycle times of accel./ decel. are too short.
Incorrect motor rated current has been set.
• Reduce the motor load.
• Use a motor with external cooling and set
the correct motor in parameter L1-01
• Check the sequence.
• Check the rated current setting.
LED Display AL FLT
Cause
Corrective Action
or
WWW.NNC.IR