3 Electrical Installation
EN 28
YASKAWA Europe
TOEP C710606 101A - V1000 MMD IP65 Motor Mounted Drive - Quick Start Guide
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring and other high-power lines.
• Separate wiring for control circuit terminals MA, MB, MC (contact output) from wiring
to other control circuit terminals.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating
faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.
• If flexible wires with ferrules are connected they might fit tightly into the terminals. To
disconnect them, grasp the wire end with a pair of pliers, release the terminal using a
straight-edge screw driver, turn the wire for about 45
and pull it gently out of the termi-
nal. For details, refer to the Technical Manual. Use this procedure for removing the wire
link between HC, H1 and H2 when the Safe Disable function is utilized.
Main Circuit Terminals
Terminal
Type
Function
L1, L2, T/L3
Filter connection
Connects line power to the built-in EMC filter.
U/T1, V/T2, W/T3
Drive output
Connects to the motor.
B1, B2
Braking resistor
For connecting a braking resistor or the braking resistor unit option.
+1, +2
DC reactor connec-
tion
Linked at shipment. Remove the link to install a DC choke.
+1, –
DC power supply
input
For connecting a DC power supply.
(2 terminals)
Ground Terminal
For 400 V class: Ground with 10
or less.
Connector is located at EMC filter (M5 screw).