6 Related Drive Parameters
YASKAWA ELECTRIC
SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual
23
6
Related Drive Parameters
The parameters in
set the drive for operation with the option. Confirm proper setting of all parameters in
before starting network communications. Refer to the manual packaged with the drive for details on setting parameters.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
Table 7 Related Parameter Settings
No.
(Hex.)
Name
Description
Values
b1-01
(0180)
Reference 1 Source
Selects the input method for frequency reference.
0: Keypad
1: Analog Input
2: Memobus/Modbus Communications
3: Option PCB
4: Pulse Train Input
Default: 1
Range: 0 to 4
(Set to 3)
b1-02
(0181)
Run Command 1 Source
Selects the input method for the Run command.
0: Keypad
1: Digital Input
2: Memobus/Modbus Communications
3: Option PCB
Default: 1
Range: 0 to 3
(Set to 3)
F6-01
(03A2)
Communication Error Selection
Selects drive response when a bUS error is detected during
communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
4: Alarm - Run at d1-04
5: Alarm - Ramp to Stop
Default: 1
Range: 0 to 5
F6-02
(03A3)
Comm External Fault (EF0) Detect
Selects the condition for external fault detection (EF0).
0: Always detected
1: Detection during run only
Default: 0
Range: 0, 1
F6-03
(03A4)
Comm External Fault (EF0) Select
Selects drive response for external fault input (EF0) detection during
option communications.
0: Ramp to Stop
1: Coast to Stop
2: Fast Stop (Use C1-09)
3: Alarm Only
Default: 1
Range: 0 to 3
F6-06
(03A7)
Torque Reference/Limit by Comm
Enabling this parameter allows d5-01 to determine whether the value is
read as the Torque Limit value (d5-01 = 0) or the Torque Reference value
(d5-01 = 1).
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
F6-07
(03A8)
MultiStep Ref Priority Select
0: MultiStep References Disabled
1: MultiStep References Enabled
Default: 0
Range: 0, 1
F6-08
(036A)
Comm Parameter Reset
@Initialize
Selects whether communication-related parameters F6-
and F7-
are set back to original default values when the drive is initialized using
parameter A1-03.
0: No Reset - Parameters retained
1: Reset - Back to factory default
Note: The setting value is not changed even when F6-08 is set to 1 and the
drive is initialized using A1-03.
Default: 0
Range: 0, 1
F6-14
(03BB)
Bus Error Auto Reset
Sets the automatic reset function for bUS [Option Communication
Errors].
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
F6-15
(0B5B)
Comm. Option Parameters Reload
Selects whether F6-
/F7-
communication-related parameters
changed are enabled.
0: Reload at Next Power Cycle
1: Reload Now
2: Cancel Reload Request
Note: F6-15 is reset to 0 after setting 1 or 2.
Default: 0
Range: 0 to 2