10 Input Assemblies (Drive Produces)
YASKAWA ELECTRIC
SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
39
MEMOBUS/Modbus Message Input (Vendor Specific YE Assy) - 150 (0x96)
Note:
This is a paired assembly (100/150).
Table 12 Reply Mapping - 150
Table 13 Error Replies - 150
Note:
Refer to the MEMOBUS/Modbus Data Table in Appendix C of the V1000 Technical Manual for a list of monitor data using the
MEMOBUS/Modbus message area.
Input Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
150
0
Function Code
1
Register Number (High Byte)
2
Register Number (Low Byte)
3
Register Data (High Byte)
4
Register Data (Low Byte)
Byte
Write Success
Read Success
Write Failure
Read Failure
Invalid Function
Code
Function
Code
Equals
Zero
0
0x10
0x03
0x90
0x83
Function Code Or-ed
with 0x80
0
1
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(High Byte)
0
2
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(Low Byte)
0
3
0
Read Data (High Byte)
0
0
0
0
4
0
Read Data (Low Byte)
Error Code
Error Code
1
0
Error Code
Description
0x01
Invalid Function Code
0x02
Invalid Register Number
0x21
Upper/Lower Limit Error
0x22
Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done yet.
Writing “Enter” when drive is running.
Attempt to write data that is read only.
Attempt to write a constant when drive is running.
During a CPF03 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.
0x23
Attempting to write during a drive undervoltage (Uv) event.
0x24
Attempting to write while the drive is storing data.