10 Input Assemblies (Drive Produces)
36
YASKAWA ELECTRIC
SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
Extended Speed Control Input - 71 (0x47)
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
71
0
At Speed
Ref from Net Ctrl from Net
Ready
Running 2
(REV)
Running 1
(FWD)
Warning
Faulted
1
Drive State
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Warning
Warning
0: No Warning Occurred
1: Warning Occurred
Running 1 (FWD)
Forward Running
0: Stop or Reverse Running
1: Forward Running
Running 2 (REV)
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Ready
Drive Ready
0: Not Ready
1: Ready
Ctrl from Net
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Ref from Net
Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network
At Speed
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
Drive State
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Speed Actual
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2
SS
(SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 2
2
= 4096 = 0x1000
Unit depends on o1-03.