78
YASKAWA
TOEP C730600 0EA Modbus TCP/IP Installation Manual
Status
Fault Declared
Status Value (
U6-98
/
U6-99
)
Description
Duplicate IP Address
bUS
1102
This node and at least one other node
have the same IP Address.
Default MAC
Address
-
1103
MAC Address programmed into the
option is not factory default setting.
Note:
Contact Yaskawa or your nearest
sales representative for more
information.
Two drive monitor parameters,
U6-98 [First Fault]
and
U6-99 [Current Fault]
assist the
user in network troubleshooting.
•
U6-98
displays the first declared fault since the last power cycle.
U6-98
is only cleared
upon drive power-up.
•
U6-99
displays the present option status.
U6-99
is cleared upon a network-issued fault
reset and upon power-up.
If another fault occurs while the original fault is still active, parameter
U6-98
retains the
original fault value and
U6-99
stores the new fault status value.
◆
Option Compatibility
You can connect a maximum of 3 options at the same time depending on the type of
option.
Note:
You can only connect one option to the GA500 and HV600. Connect the option to the CN5 connector.
Table 10.2 Option Compatibility
Option
Connector
Number of Options
Possible
PG-B3, PG-X3
CN5-B, C
2
PG-RT3
, PG-F3
CN5-C
1
DO-A3, AO-A3
CN5-A, B, and C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
SI-ES3, SI-B3, SI-M3,
SI-W3
, SI-EM3
, SI-EM3D
, SI-
EN3
, SI-EN3D
, SI-EP3,
AI-A3
, DI-A3
CN5-A
1
*1
To connect two PG options, use the CN5-C and CN5-B connectors. To connect only one PG option, use the
CN5-C connector.
*2
If you use the motor switching function, you cannot use this option.
*3
Not available with 1000-Series drive models with a capacities between 450 and 630 kW.