30
YASKAWA
SIEP C730600 0E YAI Modbus TCP/IP Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
.
F7-12
(03F0)
Gateway Address 4
Sets the static/fixed Gateway address. Parameter F7-12 sets the fourth most significant octet.
Note:
•
This parameter is only effective when
F7-13 = 0 [Address Mode at Startup = Static]
.
•
All IP Addresses must be unique.
•
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
.
1
(0 - 255)
F7-13
(03F1)
Address Startup Mode
Selects how the option address is set.
0 : Static (Use F7-01 to F7-12 to set.)
1 : BOOTP (Use network address.)
2 : DHCP (Use network address.)
Note:
You must cycle power to the drive for the changes to take effect. For non-1000 series drives,
you can set
F6-15 = 1 [Comm. Option Parameters Reload = Reload Now]
.
2
(0 - 2)
F7-14
(03F2)
Duplex Mode Selection
Selects duplex mode setting (Port 1/Port 2).
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
4 : Half/Full
5 : Auto/Half
6 : Auto/Full
7 : Full/Half
8 : Full/Auto
Note:
•
When you set this parameter to 0, 2, 3, 4, 7, or 8, you must also set
F7-15 = 0.0
.
•
This option sets the duplex mode for port 1 and port 2 as specified by these
F7-14
.
–
When 0: Half/Half
, port 1/port 2 is set to Half.
–
When 1: Auto/Auto
, port 1/port 2 is set to Auto.
–
When 2: Full/Full
, port 1/port 2 is set to Full.
–
When 3: Half/Auto
, port 1 is set to Half and port 2 is set to Auto.
–
When 4: Half/Full
, port 1 is set to Half and port 2 is set to Full.
–
When 5: Auto/Half
, port 1 is set to Auto and port 2 is set to Half.
–
When 6: Auto/Full
, port 1 is set to Auto and port 2 is set to Full.
–
When 7: Full/Half
, port 1 is set to Full and port 2 is set to Half.
–
When 8: Full/Auto
, port 1 is set to Full and port 2 is set to Auto.
1
(0 - 8)
F7-15
(03F3)
Communication Speed
Selection
Sets the communications speed (Port 1 / Port 2).
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Note:
•
F7-15
is only effective when the port is set to half or full duplex in
F7-14 [Duplex Mode
Selection]
.
•
The default setting and setting range are different for different product series.
–
1000-Series, GA700, GA800
Default: 10
Range: 10 - 102
–
GA500
Default: 10
Range: 10, 100
–
HV600
Default: 10
Range: 10, 102
•
This option sets the communication speed for port 1 and port 2 as specified by these
F7-15
settings:
–
When 10: 10/10 Mbps
, port 1/port 2 is set to 10 Mbps.
–
When 100: 100/100 Mbps
, port 1/port 2 is set to 100 Mbps.
–
When 101: 10/100 Mbps
, port 1 is set to 10 Mbps and port 2 is set to 100 Mbps.
–
When 102: 100/10 Mbps
, port 1 is set to 100 Mbps and port 2 is set to 10 Mbps.
10
(10 - 102)
F7-16
(03F4)
Timeout Value
Sets the detection time for a communications timeout.
Note:
•
Set this parameter to
0.0
to disable the connection timeout function.
•
This parameter is not available in all 1000-series drives.
•
Changes to this parameter take effect immediately. It is not necessary to cycle power on the
drive.
0.0 s
(0.0 s - 30.0 s)
H5-11
(043C)
Communications ENTER
Function Selection
(Function common to
communication option)
Sets when an Enter command is necessary to use MEMOBUS/Modbus communications to change
parameter values.
0 : Parameter changes are activated when ENTER command is written
1 : Parameter changes are activated immediately. No ENTER command is necessary.
0
(0, 1)