3 Wiring
3.1 Molded-case Circuit Breaker and Fuse
When choosing a molded-case circuit breaker and a fuse capacity, refer to
this table. The rated input current of the SERVOPACK is the nominal value
at the rated load.
Select the appropriate capacity in accordance with the specified derating.
Cutoff characteristics (25
°
C): 300% five seconds min.
SERVOPACK
Model SGDV-
Power Supply
Capacity per
SERVOPACK
(kVA)
Rated Input Current of
SERVOPACK
(A
rms
)
Rated Voltage
Main circuit
power supply
Control circuit
power supply
Fuse
MCCB
R70F
0.2
1.5
0.38
250 V
240 V
R90F
0.3
2.5
2R1F
0.7
5
2R8F
1.4
10
R70A
0.2
1.0
0.2
R90A
0.3
1.0
1R6A
0.6
2.0
2R8A
1
3.0
3R8A
1.4
3.0
5R5A
1.6
6.0
7R6A
2.3
6.0
120A
3.2
7.5
0.25
180A
4
10
200A
5.9
15
330A
7.5
25
0.3
470A
10.7
29
550A
14.6
37
590A
21.7
54
0.45
600 V
480 V
780A
29.6
73
1R9D
1.1
1.4
1.2
3R5D
2.3
2.9
5R4D
3.5
4.3
8R4D
4.5
5.8
1.4
120D
7.1
8.6
170D
11.7
14.5
210D
12.4
17.4
1.5
260D
14.4
21.7
280D
21.9
31.8
1.7
370D
30.6
43.4