7 Parameter Table
26
YASKAWA ELECTRIC
TOEP C710656 09D YASKAWA Power Regenerative Unit - R1000 Quick Start Guide
H3-09
(417H)
Terminal A2
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note:
Use DIP switch S1 to set input
terminal A2 for a current or a voltage input
signal.
H3-10
(418H)
Terminal A2
Function
Selection
Sets the function of terminal A2.
H3-11
(419H)
Terminal A2
Gain Setting
Sets the level of the input value selected in
H3-10 when 10 V (20 mA) is input at
terminal A2.
H3-12
(41AH)
Terminal A2
Bias Setting
Sets the level of the input value selected in
H3-10 when 0 V (0 or 4 mA) is input at
terminal A2.
H3-13
(41BH)
Analog Input
Filter Time
Constant
Sets a primary delay filter time constant
for terminals A1, A2, and A3. Used for
electrical noise filtering.
H3-14
(41CH)
Analog Input
Terminal Enable
Selection
1: Terminal A1 only
2: Terminal A2 only
3: Terminals A1 and A2 only
4: Terminal A3 only
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
H4: Analog Outputs
H4-01
(41DH)
Terminal FM
Monitor
Selection
Selects the data to be output through
terminal FM.
Set the desired monitor parameter to the
digits available in U
-
.
For example, enter “154” for U1-54.
H4-02
(41EH)
Terminal FM
Monitor Gain
Sets the signal level at terminal FM that is
equal to 100% of the selected monitor
value.
H4-03
(41FH)
Terminal FM
Monitor Bias
Sets the signal level at terminal FM that is
equal to 0% of the selected monitor value.
H4-04
(420H)
Terminal AM
Monitor
Selection
Selects the data to be output through
terminal AM.
Set the desired monitor parameter to the
digits available in U
-
.
For example, enter “154” for U1-54.
H4-05
(421H)
Terminal AM
Monitor Gain
Sets the signal level at terminal AM that is
equal to 100% of the selected monitor
value.
H4-06
(422H)
Terminal AM
Monitor Bias
Sets the signal level at terminal AM that is
equal to 0% of the selected monitor value.
H4-07
(423H)
Terminal FM
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
H4-08
(424H)
Terminal AM
Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
No.
(Addr.
Hex)
Name
Description
L2: Momentary Power Loss Ride-Thru
L2-01
(485H)
Momentary
Power Loss
Operation
Selection
0: Disabled. Regenerative unit trips on
Uv1 fault when power is lost.
1: Recover within the time set in L2-02.
Uv1 will be detected if power loss is
longer than L2-02.
2: Recover as long as CPU has power. Uv1
is not detected.
Note:
Even if L2-01 is set to 1 or 2, the
regenerative unit may detect a fault when
momentary-power-loss occurs during
regeneration or during no load.
L2-02
(486H)
Momentary
Power Loss
Ride-Thru Time
Sets the Power Loss Ride-Thru time.
Enabled only when L2-01 = 1 or 3.
L5: Fault Restart
L5-01
(49EH)
Number of Auto
Restart Attempts
Sets the number of times the regenerative
unit may attempt to restart after the
following faults occur: oC, oH1, oL2, ov,
Uv1.
L5-02
(49FH)
Auto Restart
Fault Output
Operation
Selection
0: Fault output not active.
1: Fault output active during restart
attempt.
L5-04
(4A0H)
Fault Reset
Interval Time
Sets the amount of time to wait between
performing fault restarts.
L5-05
(46CH)
Fault Reset
Operation
Selection
0: Continuously attempt to restart while
incrementing restart counter only at a
successful restart.
1: Attempt to restart with the interval time
set in L5-04 and increment the restart
counter with each attempt.
L8: Drive Protection
L8-02
(4AEH)
Overheat Alarm
Level
An overheat alarm occurs when heatsink
temperature exceeds the L8-02 level.
L8-03
(4AFH)
Overheat
Pre-Alarm
Operation
Selection
0: Ramp to stop. A fault is triggered.
3: Continue operation. An alarm is
triggered.
L8-10
(4B6H)
Heatsink
Cooling Fan
Operation
Selection
0: During run only. Fan operates only
during run for L8-11 seconds after stop.
1: Fan always on. Cooling fan operates
whenever the regenerative unit is powered
up.
L8-11
(4B7H)
Heatsink
Cooling Fan Off
Delay Time
Sets a delay time to shut off the cooling
fan after the Run command is removed
when L8-10 = 0.
L8-12
(4B8H)
Ambient
Temperature
Setting
Enter the ambient temperature. This value
adjusts the oL2 detection level.
L8-35
(4ECH)
Installation
Method
Selection
0: IP00 Open Type Enclosure
1: Side-by-Side Mounting
2: IP20/UL Type 1 enclosure
3: External Heatsink Installation
L8-41
(4F2H)
High Current
Alarm Selection
0: Disabled
1: Enabled. An alarm is triggered at output
currents above 150% of regenerative unit
rated current.
L8-65
(66FH)
Power Supply
Fault Detection
Selection
0: No detection
1: Stop operation (fault)
2: Continue operation (minor fault)
No.
(Addr.
Hex)
Name
Description