PVI 23TL, 28TL Installation and Operation Manual (Rev J)
DOCR-070365-J
Page
54
of
66
Protection
9. IntProtect
0010-0260
Internal
problem within
the inverter
1. One of the
inverter’s internal
protection features
was triggered
causing the inverter
to shut down.
1. Observe for 10min and
see whether the alarm is
cleared automatically.
2. If error does not clear,
contact Solectria
Customer Service.
Protection
10. Arc Protect
Inverter shuts
down due to a
possible Arc
fault concern
1. An internal Arc
fault occurred on the
DC side.
1. Have qualified Electrical
Personnel inspect wiring
section of Inverter.
2. If no issues are found,
contact Solectria
Customer Service.
2. Fault with the Arc
board.
Fault
1. IntFault0010-
150
Internal non-
critical fault
within the
inverter
1. A fault occurred
internally within the
inverter.
1. The inverter will restart
once the fault is cleared.
2. If error does not clear,
contact Solectria
Customer Service.
Table 10.1 – Troubleshooting