Parameters Available in the Setup Group
n
Setup Mode (STUP)
Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently
used parameters are selected and input into Setup Mode.
1.
To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key
until
is displayed.
2.
Select the parameter and change the setting.
lists parameters available in
the Setup group. If the desired parameter cannot be set in the Setup mode, use the
Parameter Setting mode.
Note:
1.
When parameter A1-02 (Control Method Selection) is changed, some parameter set values are also
changed automatically.
2.
Use the “Par” menu in the Programming mode to access parameters not listed in the Setup Group.
3.
Display parameters depend on A1-06.
Refer to Application Selection on page 96
Table 4.2 Setup Group Parameters
Parameter
Name
A1-02
Control Method Selection
b1-01
Frequency Reference Selection 1
b1-02
Run Command Selection 1
b1-03
Stop Method Selection
C1-01
Acceleration Time 1
C1-02
Deceleration Time 1
C6-01
Duty Selection
C6-02
Carrier Frequency Selection
d1-01
Frequency Reference 1
d1-02
Frequency Reference 2
d1-03
Frequency Reference 3
d1-04
Frequency Reference 4
d1-17
Jog Frequency Reference
E1-01
Input Voltage Reference
Parameter
Name
E1-03
V/f Pattern Selection
E1-04
Maximum Output Frequency
E1-05
Maximum Voltage
E1-06
Base Frequency
E1-09
Minimum Output Frequency
E1-13
Base Voltage
E2-01
Motor Rated Current
E2-04
Number of Motor Poles
E2-11
Motor Rate Capacity
H4-02
Terminal AM Gain Setting
L1-01
Motor Protection Function Selection
L3-04
Stall Prevention Selection during
Deceleration
4.2 The Drive and Programming Modes
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
89
4
Start-Up Programming & Operation