VAN-V19001E [V1000→GA500]
27
/35
5-3. Parameter Matching Table
The V1000 parameters have the same numbers as those of the GA500 but may be different in the setting range or factory default.
The following table lists the parameters different in the setting range or factory default.
Table 20: Parameter Matching Table
Parameter
No.
Name
V1000
GA500
Default
Your
customized
settings
Range
Default
Range
A1-00
Language
Selection
Depends
on O2-09
0 = English
1 = Japanese
2 = German
3 = French
4 = Italian
5 = Spanish
6 = Portuguese
7 = Chinese (Simplified)
Depends
on O2-09
0 = English
1 = Japanese
2 = German
3 = French
4 = Italian
5 = Spanish
6 = Portuguese
7 = Chinese (Simplified)
8 = Czech
9 = Russian
10 = Turkish
11 = Polish
12 = Greek
A1-01
Access Level
Selection
2
0 = Operation Only
1 = Custom parameters
2 = All parameters
2
0 = Operation Only
1 = User Parameters
2 = Standard
Parameters
3 = All Parameters
(Including Expert
Mode)
A1-02
Control
Method
Selection
0
0 = V/f Control
2 = Open Loop Vector
5 = OLV/PM
0
0 = V/f Control (V/f)
2 = Open Loop Vector
Control (OLV)
5 = OLV/PM
6 = AOLV/PM
8 = EZOLV
A1-03
Initialize
Parameters
0
0 = No Initialization
1110 = User Initialization
2220 = 2-Wire Initialization
3330 = 3-Wire Initialization
5550 = oPE04 error reset
0
0 = No Initialization
1110 = User Initialization
2220 = 2-Wire
Initialization
3330 = 3-Wire
Initialization
B2-01
DC Injection/
Zero Speed
Threshold
0.5
0.0 to 10.0
1.0 for
only A1-
02=6, 0.5
for other
0.0 to 10.0 Hz
B2-13
Short Circuit
Brake Time
@ Stop
0.50
0.00 to 25.50
0 for A1-
02=8,
0.50 for
other
0.00 to 25.50 s
B3-14
Bi-directional
Speed
Search
0
0 = Disabled (rotate in the
specified direction)
1 = Enabled (rotate in the
searched direction)
0
(Depends
on A1-02)
0 = Disabled (rotate in
the specified direction)
1 = Enabled (rotate in
the searched direction)