Terminal Functions
Table 5 Option Terminal Functions
Terminal
Block
Terminal
Function
Description
TB1
<1> A separate power supply is needed if the PG requires more than 200 mA to operate. Select a UL-listed class 2
power supply.
A+
A pulse signal input
• Inputs for the A channel, B channel, and Z pulses
from the PG
• Signal level matches RS-422
A–
A inverse pulse signal input
B+
B pulse signal input
B–
B inverse pulse signal input
Z+
Z pulse signal input
Z–
Z inverse pulse signal input
SD
NC pin (open)
Open connection port for use when cable shields
should not be grounded
FE
Ground
Used as the shield ground termination point.
TB2
IP
PG power supply
• Output voltage: 12.0 V
±
5% or 5.5 V
±
5%
• Max. output current: 200 mA
IG
PG power supply common
SG
Monitor signal common
• Output signal for monitoring A channel, B channel,
and Z pulses from the PG
• Signal level matches RS-422
a+
A pulse monitor signal
a–
A pulse inverse monitor signal
b+
B pulse monitor signal
b–
B pulse inverse monitor signal
z+
Z pulse monitor signal
z–
Z pulse inverse monitor signal