Digital Operator Display
Fault Name
CPF22
Hybrid IC Failure
Cause
Possible Solution
Hybrid IC failure on the power board
• Cycle power to the drive.
• If the problem continues, replace the power board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the power board.
Digital Operator Display
Fault Name
CPF23
Control Board Connection Error
Connection error between the control board and the drive
Cause
Possible Solution
Hardware is damaged
• Turn off the power and check the connection between the control board and the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Digital Operator Display
Fault Name
CPF24
Drive Unit Signal Fault
The drive capacity cannot be detected correctly (drive capacity is checked when the drive is powered up).
Cause
Possible Solution
Hardware is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Digital Operator Display
Fault Name
CPF25
Terminal Board Not Connected
Cause
Possible Solution
Terminal board is not connected correctly
Reconnect the terminal board to the connector on the drive, then cycle the power to the drive.
Digital Operator Display
Fault Name
to
to
CPF26 to CPF35
CPF40 to CPF43
Control Circuit Error
CPU error
Cause
Possible Solution
Hardware is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Digital Operator Display
Fault Name
E5
MECHATROLINK Watchdog Timer Error
The watchdog timed out.
Cause
Possible Solution
Data has not been received from the PLC
Execute DISCONNECT or ALM_CLR, then issue a CONNECT command or SYNC_SET command and
proceed to phase 3. Refer to the SI-T3 Option Technical Manual for more details on troubleshooting.
Digital Operator Display
Fault Name
EF0
Option Card External Fault
An external fault condition is present.
Cause
Possible Solution
An external fault was received from the PLC
and F6-03 is set to a value other than 3.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Problem with the PLC program
Check the PLC program and correct problems.
Digital Operator Display
Fault Name
EF1
External Fault (input terminal S1)
External fault at multi-function input terminal S1.
EF2
External Fault (input terminal S2)
External fault at multi-function input terminal S2.
6.4 Fault Detection
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
297
6
Troubleshooting
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......