Setting 1: -10 to 10 V
u
F6 and F7: Communication Option Card
These parameters configure communication option cards and communication fault detection methods.
Some parameters apply to all communication option cards and some parameters apply to certain network options only. The
option cards are applicable to the parameter rows marked with an “O”.
Comm.
Protocol
Parameter Range
F6-01 to
F6-03
F6-04
F6-06 to
F6-08
F6-10 to
F6-14
F6-20,
F6-21
F6-22
F6-23 to
F6-26
F6-30 to
F6-32
F6-35,
F6-36
F6-45 to
F6-49
F6-50 to
F6-63
F7-01 to
F7-15
F7-16
F7-17 to
F7-42
CC-Link
O
O
O
O
–
–
–
–
–
–
–
–
–
–
MECHA-
TROLINK-II
O
–
O
–
O
O
O
–
–
–
–
–
–
–
MECHA-
TROLINK-
III
O
–
O
–
O
–
O
–
–
–
–
–
–
–
PROFIBUS-
DP
O
–
O
–
–
–
–
O
–
–
–
–
–
–
CANopen
O
–
O
–
–
–
–
–
O
–
–
–
–
–
EtherCAT
O
–
O
–
–
–
–
–
–
–
–
–
–
–
BACnet
O
–
–
–
–
–
–
–
–
O
–
–
–
–
DeviceNet
O
–
O
–
–
–
–
–
–
–
O
–
–
–
LonWorks
O
–
O
–
–
–
–
–
–
–
–
–
–
–
Modbus
TCP/IP
O
–
O
–
–
–
–
–
–
–
–
O
O
–
PROFINET
O
–
O
–
–
–
–
–
–
–
–
O
–
O
EtherNet/IP
O
–
O
–
–
–
–
–
–
–
–
O
–
O
n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error Operation Selection
0 to 5
1
Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)
Setting 1: Coast to Stop
Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)
Setting 3: Alarm Only (Continue Operation)
Setting 4: Alarm Only (Continue Operation Using the Frequency Reference Set in d1-04)
Setting 5: Alarm and Ramp to Stop
Note:
Settings 4 and 5 available in drive software versions PRG: 8503 and later.
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Detection Selection
0, 1
0
Setting 0: Always Detected
Setting 1: Detection during Run Only
5.6 F: Option Settings
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
199
5
Parameter Details
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......