1.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
115
Pa
ra
m
et
er D
et
ai
ls
1
Setting a Custom V/f Pattern
Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters
E1-04 to E1-13.
When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be
equal to V/f pattern 0 of the predefined patterns.
■
V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if
E1-03 =< 15 or set up a custom V/f pattern as shown in
when E1-03 = F.
No.
<1> Default setting is determined by the control mode.
<2> When using PM Open Loop Vector, the default setting is determined by the motor code set to E5-01.
<3> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
<4> In OLV for PM E1-09 specifies the start frequency for short circuit braking at stop. Refer to
for details.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz
E1-05
Maximum Voltage
0.0 to 255.0 V
E1-06
Base Frequency
0.0 to 400.0
Hz
E1-07
Middle Output Frequency
0.0 to 400.0 Hz
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V
E1-09
Minimum Output Frequency
0.0 to 400.0 Hz
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V
E1-11
Middle Output Frequency 2
0.0 to 400.0 Hz
0.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 to 255.0
0.0 V
E1-13
Base Voltage
0.0 to 255.0 Hz
0.0 V
Содержание OYMC V1000
Страница 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Страница 294: ...2 12 Self Diagnostics 294 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Страница 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...