5-3
156527-1CD
HW1480826
I/O Expansion European
Standard (PNP)
5 I/O Signal Allocation
5.1 I/O Module Setting
6. Confirm the status of the mounted I/O module.
– Only the I/O modules mounted on DX100 are displayed. Confirm
that each station (ST#) indicates the actual mounted status of the
I/O module.
– The following table lists the meanings of each line.
– In the example shown on the display, the configuration of boards are
as follows.
ST#03: JARCR-XOI02B board
(digital input 40 points, digital output 40 points).
Switch S1: set to 3 (This value becomes the ST#).
ST#14: JZNC-YIU02-E unit
(digital input 40 points, digital output 40 points).
This unit is fixed to ST#14.
7. Press [ENTER].
– The confirmation dialog box appears.
8. Select “YES.”
– When the mounted status of an I/O module is correct, select “YES.”
The I/O module setting is updated, and an I/O module is added.
ST#
Station address of I/O module
DI
Number of digital input points
1)
1 A hyphen "-" indicates the corresponding I/O module is not
mounted.
DO
Number of digital output points
AI
Number of analog input points
AO
Number of analog output points
BOARD
Circuit board type
2)
2 If the system cannot recognize the circuit board type, “*****” is
shown. No problem will occur as long as the values displayed in
DI, DO, AI, and AO are correct.
21/36