YASKAWA ELECTRIC
TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide
33
8 Drive Configuration Properties
8
Drive Configuration Properties
◆
Drive Related Network Configuration Properties
Table 5 Drive Configuration Properties
Name
Variable Type
Description
nciMaxSpeed
SNVT_lev_percent Maximum Motor Speed
nciMinSpeed
SNVT_lev_percent
Minimum Motor Speed
nciSndHrtBt
SNVT_time_sec
Send Heartbeat Time
nciNmlSpeed
SNVT_rpm
Nominal Motor Speed in RPM
(Motor Rated Rotation Frequency)
nciNmlFreq
SNVT_freq_hz
Nominal Motor Frequency (Motor Rated Frequency)
nciRampUpTm
SNVT_time_sec
Drive Ramp Up Time (Drive Acceleration Time)
nciRampDownTm
SNVT_time_sec
Minimum Ramp Down Time
(Minimum Deceleration Time)
nciRcvHrtBt
SNVT_time_sec
Receive Heartbeat Time
nciMinOutTm
SNVT_time_sec
Minimum Send Time
nciLocation
SNVT_str_asc
Location Label
nciPwupOutTm
SNVT_time_sec
Power delay Timer
nciFreqMinDelta1
SNVT_lev_percent
Output Frequency Monitor Minimum Change Range
Setting 1 (nciFreqMinDelta1)
nciFreqMinDelta2
SNVT_ freq_hz
Output Frequency Monitor Minimum Change Range
Setting 2 (nciFreqMinDelta2)
nciDrvSpeedScale
SNVT_lev_percent
nviDrvSpeedScale Default
nciInvSetFreq
SNVT_ freq_hz
nviInvSetFreq Default
nciDrvSpeedRef
SNVT_lev_percent
nviDrvSpeedRef Default
nciDrvEngylimit
SNVT_elec_kwh_l
Cumulative Power Monitor Upper Limit:
nciDrvEngylimit
nciEngyMinDelta
SNVT_elec_kwh_l
Cumulative Power Monitor Minimum Change Range
Setting
nciOpMode
SNVT_count
Reference Selection Mode
nciDrvRunMode
SNVT_switch
Run Command Status Mode