YASKAWA AC Drive L1000V Technical Manual
B.3 Parameter Table
B.3
Parameter Table
u
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
n
A1: Initialization Parameters
n
A2: User Parameters
u
b: Application
Application parameters configure the source of the Up/Down command, timer functions, the Dwell function, the Droop
Control function, Energy Savings, and a variety of other application-related settings.
n
b1: Operation Mode Selection
No.(Addr.)
Name
Description
Setting
Page
A1-00
(100H)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
LCD Operator Language
Selection
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
Default: 0
Min: 0
Max: 7
A1-01
(101H)
Access Level Selection
0: View and set A1-01 and A1-04. U
-
parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Min: 0
Max: 2
A1-02
(102H)
Control Method Selection
0: V/f Control
2: Open Loop Vector Control
Default: 0
Min: 0
Max: 7
A1-03
(103H)
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
5550: oPE04 error reset
Default: 0
Min: 0
Max: 5550
A1-04
(104H)
Password
When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
through A1-03, and A2-01 through A2-33 cannot be changed.
Default: 0000
Min: 0000
Max: 9999
A1-05
(105H)
Password Setting
No.(Addr.)
Name
Description
Setting
Page
A2-01 to
A2-32
(106 to 125H)
<5> Default setting is determined by the control mode (A1-02).
User Parameters 1 to 32
Parameters that were recently edited are listed here. The user can also select parameters to
appear here for quick access.
Min: b1-01
Max: S6-16
A2-33
(126H)
User Parameter Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to A2-
17 through A2-32 for quick access.
Default: 1
Min: 0
Max: 1
No.(Addr.)
Name
Description
Setting
Page
b1-02
(181H)
Up/Down Command Selection
0: Digital operator
1: Digital input terminals
Default: 1
Min: 0
Max: 1
b1-03
(182H)
Stopping Method Selection
0: Ramp to stop
1: Coast to stop
Default: 0
Min: 0
Max: 1
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...