127
5
Setting 79: Brake feedback
This input allows the drive to monitor the brake operation and issue a fault if the brake status does not match the brake
command (digital output set to H2-
= 50).
u
H2: Multi-Function Digital Outputs
n
H2-01 to H2-03: Terminals MA-MB-MC, MD-ME-MF and P1-PC Function Selection
The drive has three multi-function output terminals. Two are relay outputs (M ) and one is a photocoupler output (P1-
PC).
lists the functions available for theses terminals using H2-01 through H2-03.
Table 5.7 Multi-Function Digital Output Terminal Settings
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Setting 1: Zero Speed
Terminal closes whenever the output speed or motor speed (simple closed loop) falls below the minimum output speed
set to E1-09 or S1-01.
Figure 5.12
Figure 5.12 Zero-Speed Time Chart
No.
Parameter Name
Setting Range
Default
H2-01
Terminals MA-MB-MC Function Selection
0 to 158
E: Fault
H2-02
Terminals P1-PC Function Selection
0 to 158
6: Drive Ready
H2-03
Terminals MD-ME-MF Function Selection
0 to 158
50: Brake Control
Setting
Function
Page
Setting
Function
Page
0
During Run
15
Speed Detection 3
1
Zero Speed
16
Speed Detection 4
2
Speed Agree 1
18
Torque Detection 2
3
User-set Speed Agree 1
1A
During Reverse
4
Speed Detection 1
1B
During Baseblock 2 (N.C.)
5
Speed Detection 2
1E
Restart Enabled
6
Drive Ready
1F
Motor Overload Alarm (oL1)
7
DC Bus Undervoltage
20
Drive Overheat Pre-alarm (oH)
8
During Baseblock (N.O.)
2F
Maintenance Period
B
Torque Detection 1
30
During Torque Limit
E
Fault
37
During Frequency Output
F
Not used (Through Mode)
50
Brake Control
10
Minor Fault
51
Output Contactor Control
11
Fault Reset Command Active
54
Light Load Direction
12
Timer Output
55
Light Load Direction Detection Status
13
Speed Agree 2
58
Safe Disable Status
14
User-set Speed Agree 2
100 to 158
Functions 0 to 58 with Inverse Output
Status
Description
Open
Drive is stopped.
Closed
An Up/Down command is input or the drive is during deceleration or during DC injection.
Status
Description
Open
The operating speed is faster than the minimum output frequency (E1-09) and the zero speed level at stop (S1-01).
Closed
The operating speed is below the minimum output frequency (E1-09) and the zero speed level at stop (S1-01).
OFF
Output speed
or
motor speed
Zero Speed
ON
E1-09 (Max. Output Frequency) or
S1-01 (Zero Speed Level)
common̲
TMonly
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...