5.7 H: Terminal Functions
130
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
Setting 8: During baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While in baseblock, output transistors do not switch and no
main circuit voltage is output.
Setting B, 18: Torque detection 1, Torque detection 2
These digital output functions to signal an overtorque or undertorque situation to an external device.
Set up the torque detection levels and select the output function from the table below. Refer to
for details.
Setting E: Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting F: Not used (Through mode)
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function
in the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or
MEMOBUS/Modbus communications.
Setting 10: Minor fault
Output closes when a minor fault condition is present.
Setting 11: Fault reset command active
Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.
Setting 12: Timer output
This setting configures a digital output terminal as output for the timer function. Refer to
for details.
Setting 13: Speed agree 2 (f
ref
/f
out
agree 2)
Closes whenever the actual output speed or motor speed (simple closed loop) is within the speed agree width (L4-04) of
the current speed reference, regardless of the direction.
Figure 5.17
Figure 5.17 Speed Agree 2 Time Chart
Status
Description
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Setting
Status
Description
B
Closed
Torque detection 1 :
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-02 for longer than
the time specified in parameter L6-03.
18
Closed
Torque detection 2 :
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-05 for longer than
the time specified in parameter L6-06.
Status
Description
Open
Output speed or motor speed does not match the speed reference while the drive is running.
Closed
Output speed or motor speed is within the range of speed reference ±L4-04.
L4-04
L4-04
Speed
reference
Speed Agree 2
ON
OFF
Output speed
or motor speed
common̲
TMonly
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...