5.4 d: Reference Settings
118
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
n
d1-20, d1-21, d1-22: Intermediate Speeds 1 to 3
Sets intermediate speeds 1 through 3.
n
d1-23: Releveling Speed
Sets the releveling speed when a multi-function input terminal is programmed for “Releveling speed” (H1-
= 52).
n
d1-24: Inspection Operation Speed
Sets the inspection speed when a multi-function input terminal is programmed for “Inspection speed” (H1-
= 54). A
description of the inspection speed can be found in
Inspection Operation on page 89
.
n
d1-25: Rescue Operation Speed
Determines the speed during Rescue Operation. Refer to
n
d1-26: Leveling Speed
Sets the inspection speed when a multi-function input terminal is programmed for “Leveling speed” (H1-
= 53).
n
d1-28: Leveling Speed Detection Level
When the speed priority selection in d1-18 is set to “0” or “3” and the speed reference value falls below the level set in
d1-28, the drive interprets the selected speed as leveling speed. This parameter must be set to use the Speed Control Loop
setting 3 when d1-18 = 0/3. Refer to
C5: Speed Control Loop on page 114
n
d1-29: Inspection Speed Detection Level
When the speed priority selection in d1-18 is set to “0” or “3” and the speed reference value is below the level set in d1-
29 but higher than the level set in d1-28, the drive interprets the selected speed as inspection speed. This parameter must
be set to use the Inspection Operation function when d1-18 = 0/3. Refer to
Inspection Operation on page 89
for details.
No.
Name
Setting Range
Default
d1-20
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit
for details.
Intermediate Speed 1
0.00 to 120.00 Hz
0.00 Hz
d1-21
Intermediate Speed 2
0.00 to 120.00 Hz
0.00 Hz
d1-22
Intermediate Speed 3
0.00 to 120.00 Hz
0.00 Hz
No.
Name
Setting Range
Default
d1-23
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit
for details.
Releveling Speed
0.00 to 120.00 Hz
0.00 Hz
No.
Name
Setting Range
Default
d1-24
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit
for details.
Inspection Operation Speed
0.00 to 120.00 Hz
0.00 Hz
No.
Name
Setting Range
Default
d1-25
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit
for details.
Rescue Operation Speed
0.00 to 15.00 Hz
5.00 Hz
No.
Name
Setting Range
Default
d1-26
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Defaults and Setting Ranges by Display Unit
for details.
Leveling Speed
0.00 to 120.00 Hz
4.00 Hz
No.
Name
Setting Range
Default
d1-28
Leveling Speed Detection Level
0.00 to 120.00 Hz
0.00 Hz
No.
Name
Setting Range
Default
d1-29
Inspection Speed Detection Level
0.00 to 120.00 Hz
0.00 Hz
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...