L1-02: Motor Overload Protection Time
No.
(Hex.)
Name
Description
Default
(Range)
L1-02
(0481)
Expert
Motor Overload Protection
Time
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the
motor. Usually it is not necessary to change this setting.
1.0 min
(0.1 - 5.0 min)
Set the overload tolerance time to the length of time that the motor can operate at 150% load from continuous
operation at 100% load.
When the motor operates at 150% load continuously for 1 minute after continuous operation at 100% load (hot
start), the default setting triggers the electronic thermal protector.
shows an example of the electronic thermal protector operation time. Motor overload protection
operates in the range between a cold start and a hot start.
This example shows a general-purpose motor operating at the base frequency with
L1-02
set to 1.0 min.
•
Cold start
Shows the motor protection operation time characteristics when the overload occurs immediately after starting
operation from a complete stop.
•
Hot start
Shows the motor protection operation time characteristics when overload occurs from continuous operation
below the motor rated current.
Figure 12.27 Protection Operation Time for a General-purpose Motor at Rated Output Frequency
■
L1-13: Motor Overload Memory Selection
No.
(Hex.)
Name
Description
Default
(Range)
L1-13
(046D)
Expert
Motor Overload Memory
Selection
Sets the function that keeps the current electronic thermal protector value when the drive stops
receiving power.
1
(0, 1)
0 : Disabled
1 : Enabled
Sets if the drive will calculate the motor again when the drive is energized again.
◆
L2: Power Loss Ride Through (Undervoltage Detection)
■
L2-05: Undervoltage Detection Lvl (Uv1)
No.
(Hex.)
Name
Description
Default
(Range)
L2-05
(0489)
Expert
Undervoltage Detection Lvl
(Uv1)
Sets the voltage at which a
Uv1 [DC Bus Undervoltage]
fault is triggered. Usually it is not
necessary to change this setting.
Determined by E1-01
(400 V Class: 300 - 420 V)
NOTICE:
Damage to Equipment. When you set this parameter to a value lower than the default, you must install an AC reactor
on the input side of the power supply. If you do not install an AC reactor, it will cause damage to the drive circuitry.
V/f
OLV
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...